 RHAA036(Node Name): Error has been responded for device read command (Error Code: (Decimal)[(Hex)] There are out of range devices)

Error Details

[RHAA036(Node Name): Error has been responded for device read command (Error Code: (Decimal)[(Hex)] There are out of range devices] error has appeared on the screen of GP3000 series.

Causes

1. There is a possibility that Device/PLC cannot recognize the Read request of the address that has been set by GP unit.
2. It might have been set to request the address that is out of the address range of Device/PLC by the GP unit.

Countermeasures

1. Please set the Device/PLC settings of GP side as same as the Device/PLC currently connected.

-> Checking the Device/PLC on the GP unit

->Changing Device/PLC Settings on the GP-Pro EX (Software)

2. If the error has occurred in all screens, the cause could be the part that is common to all screens. Please check the addresses that had been set by functions that operate in all screens, such as System Data Area, Alarm, Global D-script, Global Window and Sampling (Historical Trend Graph).
3. Please check the settings of the screen that the error occurred. Check if the addresses set is within the range of Device/PLC addresses in use.

About the receiving error code
This is an error code returned from Device/PLC. Please refer to the manual of the each Device/PLC for the error details.