 RGE*050_Different ID unit connected.

Error Description

Error message says [RGE*050_Different ID unit connected] on the screen of the AGP3000 Series.

Cause
The project file may not have downloaded properly.

Solution
Please send the project file again after checking the model number of the connected I/O modules.
1.
Please open [System Settings Window] and click [I/O Driver Settings] on [Peripheral Settings].



2. Please check that the model number of the I/O module in [I/O Driver Settings] is the same as the connected module. If not, please match the models.