 The Green LED on the AGP3000 is blinking.

Error Description

The Green LED on the AGP3000 is blinking.

Cause
The Logic Program is in [STOP] status.

Solution
Starting the Logic Program with GP-Pro EX (Editor) -> See A
Starting the Logic Program Using the AGP's Offline Menu -> See B

A) Using GP-Pro EX (Editor)
In the GP Pro EX Editor, go to [System Settings Window] -> [Main Unit Settings/Display Unit] -> [Logic Settings] tab. Select [Run] in [Run at Start Up].

B) Using the AGP Offline Menu
Go into Offline Mode, and open [Main Unit Settings] -> [Logic Settings]. Select [Run] next to [Run at Start Up].