Save to CF/USB
Select whether to record from a video camera and save on a CF
Card or USB storage.
Save in
Select a location to save a movie file from [CF] and [USB].
File Size
Specify the size of each movie file to be saved. The range is
from 1 to 512MB. Any pictures that exceed the specified file size
are automatically saved in the next file. The file uses the name
based on the timestamp (year, month, date, hours, minutes, seconds)
when the file is created.
Number of Files
Specify the number of video files to save in a folder. The
settings range from 1 to 100.
User set string
Specify the character string to be included in the folder and
file names for the saved video files. You can specify up to two
single-byte alphanumeric characters.
-
The file name is the user-defined string
(maximum two characters) + time stamp.
(For example, if the user-defined string is "MC", the date is May
27, 2006, and the time is 15:23:46, then the file name is
"MC060527_152346.SDX".
-
If the user does not specify a string, the
folder name will be "NO-NAME" and only the time stamp
(year, month, day, hour, minute, second when the file was saved)
will appear in the file name.
Direct
Specify the string by entering it here.
Indirect
Specify the address used for saving the file and for specifying
the strings as user set strings. You can change any file name on
the connection device. Use a sequence of 3 Words from the specified
address.
Turn ON bit 0 to save the codes in the
following address as "user set string".
Save the string codes. The procedure for
saving text codes differs depending on the connection devices.
Once Bit 0 in the [Control] Address is set to
ON, Bit 0 in the [Status] Address is turned ON.
Specifying user set strings while saving to the CF Card or USB
storage is in progress will result in an error and bit 15 will turn
ON.
-
Bit 0 and bit 15 of the [Status] address are
turned OFF when bit 0 of the [Control] address is turned OFF.
-
If a 32-bit device is specified, only the
bottom 16 bits are used.
-
If you copy a value of system variable
#H_LocalName to [User Set String] using D-Script and set [Control]
ON, the folder of Display unit name will be created. When saving
multiple Displays' videos, you can easily determine which Display's
data is in a folder.
Control Word Address
Specify the address for controlling save operations. Use a
sequence of 3 Words from the specified address.
Turn ON bit 0 to start recording (start
saving to CF/USB). Turn OFF the bit to stop recording.
Timing Chart for Saving on
CF/USB
The CF/USB save status and error status are
saved.
Save authorization bits are turned ON when the display unit's power
is turned on.
The error status indicates the following conditions.
Error Code
0
|
Completed Successfully
|
—
|
1 to 3
|
Reserved
|
—
|
4
|
No CF Card
|
The CF Card/USB storage is not inserted in the
display unit, or the CF Card cover is not closed.
|
USB Storage is absent
|
5
|
CF Write Error
|
Writing data to the CF Card/USB storage failed
or there is not enough free space.
|
USB storage error
|
6
|
Reserved
|
—
|
7
|
CF Card Error
|
The CF Card/USB storage device is invalid,
unformatted, or the media inserted is not a CF Card/USB
storage.
|
USB storage error
|
8 to 13
|
Reserved
|
—
|
14
|
Playing
|
Saving to CF/USB was initiated while movie play
was in progress.
|
15
|
Reserved
|
—
|
If a file is successfully saved, the address
is increased by one. You can see how many files have been saved up
to that point. Files currently being saved are not counted. The
number of files are updated when:
-
The power is turned on
-
CF Card/USB storage is inserted
-
[Indirect] is selected when setting the [User Set
String], or the folder name is changed. Only movie files (.SDX) are
counted.
Loop
Set the operation to be initiated after the movie files have
been saved as specified in [Number of Files].
Disable
After all the specified files have been saved (the MAX bit is
turned ON), no more files can be saved. to resume saving, delete
movie files or specify files saved in another folder and turn ON
the resume bit. The MAX bit turns OFF.
Enable
After all the specified files have been saved (the MAX bit is
turned ON), no more files can be saved. When the resume bit is
turned ON, the oldest file is deleted and a new file is saved.
Auto
Once all the specified files have been saved (the MAX bit is
turned ON), the files are deleted starting with the oldest file,
and new files are saved.