T.3.1.3 Can the Display Unit enter offline mode?
Cause
If the switches do not respond even after self-diagnosis in
offline mode, the GP unit may be faulty.
Solution
Conduct the self-diagnosis of the GP unit in
offline mode to determine whether the problem is in the GP or
not.
-
Correct an analog touch panel. (Setup calibration)
For the setting procedure, see the following.
M.8.2 Calibration
Touch Panel
-
Select the [Check Touch Panel] option and check
that the touched area lights up properly. For the checking
procedure, see the following.
M.8.1 Touch
Panel Check
-
If the phenomenon continues after steps (1) and
(2), the GP unit may be faulty. Please contact the Pro-face
customer care center.
T.11.2 Telephone
Contact
When the GP cannot enter offline mode, try
the following measures.
-
The system menu
used to enter offline mode may be set not to be displayed. If the
system menu does not appear, select [Menu and Error Settings] in
[Display Unit] with GP-Pro EX and set the option for [Show System
Menu] to show the system menu, and then transfer the project file
again.
5.3.2.3
Display Unit [Display] - Menu and Error Settings
If the GP can enter offline mode after the project file is
transferred, follow the steps for when the GP can enter offline
mode above.
-
If the GP cannot enter offline mode even after step
(1), the display unit may be faulty. Please contact the Pro-face
customer care center.
T.11.2 Telephone
Contact
|