Error No.
|
Error Message
|
Cause and Solution
|
001
|
Invalid model
|
The specified module type is not supported.
The project file may not have been sent
correctly. Transfer the project file again.
|
002
|
Setting value error
|
The type of the variable assigned to the
terminal is invalid, or the terminal setting is invalid.
The project file may not have been sent
correctly. Transfer the project file again.
|
003
|
Device out-of-range error
|
The variable address assigned to the terminal
is invalid.
The project file might not have been sent
properly. Transfer the project file again.
|
004
|
Too many term. setting
|
The number of terminals is invalid. (The number
of terminals is excessive.) The project file may not have been sent
correctly. Transfer the project file again.
|
005
|
Terminal setting order error
|
The terminal numbers are not arranged in
ascending order.
The project file may not have been sent
correctly. Transfer the project file again.
|
006
|
Terminal registry short
|
The number of terminals is invalid. (The number
of terminals is insufficient.)
The project file may not have been sent
correctly. Transfer the project file again.
|
007
|
Module settings duplicated
|
Module registration is duplicated.
The project file may not have been sent
correctly. Transfer the project file again.
|
008
|
Excess module settings
|
The number of modules is invalid. (The number
of terminals is excessive.)
The project file may not have been sent
correctly. Transfer the project file again.
|
009
|
Driver settings duplicated
|
Driver registration is duplicated.
The project file may not have been sent
correctly. Transfer the project file again.
|
010
|
I/O settings inconsistent
|
The terminal setting is invalid. (The I/O
setting in the module does not match.)
The project file may not have been sent
correctly. Transfer the project file again.
|
011
|
Bit/Integer type inconsistent
|
The terminal setting is invalid. (The variable
type setting in the module does not match.)
The project file may not have been sent
correctly. Transfer the project file again.
|
012
|
Setting level value error
|
The driver is invalid.
The project file may not have been sent
correctly. Transfer the project file again.
|
013
|
Data obtaining address error
|
The driver information or controller
information is invalid.
The project file might not have been sent
properly. Transfer the project file again.
|
014
|
Invalid driver ID
|
Because an error occurred during driver/module
registration, the driver/module has not been registered.
The project file may not have been sent
correctly. Transfer the project file again.
|
015
|
Module setting order error
|
The module numbers are not arranged in
ascending order.
The project file might not have been sent
properly. Transfer the project file again.
|
016
|
File version mismatch
|
The driver file version does not match.
The project file may not have been sent
correctly. Transfer the project file again.
|
050
|
I/O board ID mismatch
|
Wrong I/O board is inserted. The display type
might not be correct. Check the Display Unit type and transfer the
project file again.
|
051
|
Unsupported model
|
The model does not support this driver. The
display type might not be correct. Check the Display Unit type and
transfer the project file again.
|
052
|
I/O board init. error
|
The system failed during I/O board
initialization.
The project file may not have been sent
correctly. Transfer the project file again. If this error persists,
the GP unit may be faulty. Please contact the Pro-face customer
care center.
|
100
|
Module init. error
|
The module may not be properly connected.
Reconnect the module and turn the power on again. If this error
persists, the GP unit may be faulty. Please contact the Pro-face
customer care center.
|
101
|
Module init. resp err
|
102
|
Module init. send err
|
103
|
Module init. rcv. err
|
104
|
Module init. end err
|
105
|
Module connections err
|
The connected I/O board does not match. The
display model may be different. Check the display model, and
transfer the project file again.
|
106
|
Unsupported module
|
The connected module is not supported. Remove
the unsupported module and then turn ON electric power again.
|
107
|
Mode setting error
|
Mode setting value is faulty. The project file
might not have been sent properly. Transfer the project file
again.
|
108
|
Analog data range error
|
Upper limit and lower limit setting values of
the analogue module are faulty. The project file might not have
been sent properly. Transfer the project file again.
|
109
|
Module settings error
|
The module does not operate due to the data
mismatch between the connected module and the set data. The setup
information in the project and the connected module are different.
Connect the specified module, and turn ON the power switch
again.
|
120
|
Module validation err
|
There is a mismatch between a connected module
and the set data, however the module is partially running. The
setup information in the project and the connected module are
different. Connect the specified module, and turn ON the power
switch again.
|
121
|
Module response error
|
The module may not be properly connected.
Reconnect the module and turn the power on again. If this error
persists, the GP unit may be faulty. Please contact the Pro-face
customer care center.
|
122
|
Module send error
|
123
|
Module receive error
|
124
|
Module comm. setting
|
Difficulties in transmission data. The module
may not be properly connected. Reconnect the module and turn the
power on again. The display unit may be faulty. Please contact the
Pro-face customer care center.
|
125
|
Module ACK error
|
The module may not be properly connected.
Reconnect the module and turn the power on again. The display unit
may be faulty. Please contact the Pro-face customer care
center.
|
126
|
Module comm. error
|
127
|
Analog output error
|
Analogue output request flag write is not
completed. The project file may not have been sent correctly.
Transfer the project file again. If this error persists, the GP
unit may be faulty. Please contact the Pro-face customer care
center.
|
128
|
Output data error
|
The output data is out of the setting range, or
the data output is stopped. Output data within the setting range.
This error code continues appearing until the controller is
reset.
|
129
|
Analog power error
|
An external power supply is not connected to
the analog module. Connect a power supply to the analog module.
This error code continues appearing until the controller is
reset.
|
130
|
Input data error
|
The input data is out of the setting range, or
the data input is stopped. Input data within the setting range. Or
the analogue input cable might be damaged. Connect an undamaged
analogue input cable. This error code continues appearing until the
controller is reset.
|
200
|
Word read error
|
The system failed while reading integer-type
terminal data.
The project file may not have been sent
correctly. Transfer the project file again.
|
201
|
Bit read error
|
The system failed while reading bit-type
terminal data.
The project file may not have been sent
correctly. Transfer the project file again.
|
202
|
Word write error
|
The system failed while writing integer-type
terminal data.
The project file might not have been sent
properly. Transfer the project file again.
|
203
|
Bit write error
|
The system failed while writing bit-type
terminal data.
The project file may not have been sent
correctly. Transfer the project file again.
|