Error No.
|
Error Message
|
Cause and Solution
|
RGE*002
|
Invalid value
|
The data type of the symbol variable assigned
to the I/O is illegal. The I/O setting value is illegal. When this
error occurs, transfer the program again.
|
RGE*003
|
Out of device range
|
The address of the symbol variable assigned to
the I/O is out of range. When this error occurs, transfer the
program again.
|
RGE*004
|
Duplicate terminals
|
The number of I/O terminals exceeds the limit
(6 bit inputs and 2 bit outputs). When this error occurs, transfer
the program again.
|
RGE*005
|
Invalid terminal order
|
The I/O terminal numbers are not specified in
ascending order. When this error occurs, transfer the program
again.
|
RGE*006
|
Not enough terminals
|
The number of I/O terminals is not appropriate
(insufficient). When this error occurs, transfer the program
again.
|
RGE*009
|
Repeat driver setting
|
The driver has been registered twice. When this
error occurs, transfer the program again.
|
RGE*011
|
Bit/Word format mismatch
|
The variable type specified in the I/O is
incorrect. Transfer the project data again.
|
RGE*012
|
Invalid level
|
Something is wrong with the I/O driver.
Transfer the project data again.
|
RGE*013
|
Invalid address
|
The I/O driver information is incorrect.
Transfer the project data again.
The controller information is incorrect. Transfer the project data
again.
|
RGE*014
|
Driver/Unit unregistered
|
The I/O driver or I/O is not registered.
Transfer the project data again.
|
RGE*050
|
I/O board ID mismatch
|
The I/O board being connected is different from
the I/O board in the project. Transfer the project data again.
|
RGE*100
|
Input chatter
|
Chattering occurred during the input from the
DIO board. This may be caused by noise or GP unit failure. If this
error occurs frequently, the unit may be faulty. Please contact the
Pro-face customer care center. This error code continues appearing
until the controller is reset.
|
RGE*101
|
DIO write error
|
Although data was output to the DIO board, it
was not output when the output result was fed back. This may be
caused by noise or GP unit failure. If this error occurs
frequently, the unit may be faulty. Please contact the Pro-face
customer care center. This error code continues appearing until the
controller is reset.
|