Error No.
|
Error Message
|
Cause and Solution
|
|
RYAA001
|
The specified shared memory already exists.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA002
|
The specified shared memory does not exist.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA003
|
A shared memory already exists, but its memory
size is less than specified.
|
Close the other application programs or restart
the OS.
|
|
RYAA004
|
Cannot create a shared memory due to
insufficiency of memory or resource.
|
Close the other application programs or restart
the OS.
|
|
RYAA005
|
Could not start TdasEngine because it is
already in execution or termination.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA006
|
Could not stop TdasEngine because it is already
in suspension or termination.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA007
|
Could not register the operation in
TdasEngine.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA008
|
Cannot execute State Transition of TdaInfo
because a small service is now in transition.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA009
|
The device name ( **** ) specified as the
destination Node does not exist.
|
The defined names of connected devices are
different between the master and slave display units. The connected
devices names must match.
|
|
RYAA010
|
Cannot execute the operation due to the invalid
state of the small service.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA011
|
Cannot execute the operation because the small
service is not in operation.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA012
|
Cannot execute the operation because the small
service is in error suspension.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA013
|
The I/F of an unsupported small service was
called.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA016
|
Could not register the item because of
insufficient memory.
|
Close the other application programs or restart
the OS.
|
|
RYAA017
|
Accessed a device in which no item is
registered.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA018
|
Accessed an out-of-range device.
|
An attempt was made to access a device outside
the address range.
|
|
RYAA019
|
Failed to register the specified cluster
because an invalid item is specified in it.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA020
|
The specified data type is invalid.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA021
|
The specified access type is illegal.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA022
|
The specified data type is illegal.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA023
|
The no. of data you specified is too many to
write. (Please reduce it to **** or fewer.)
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA024
|
The operation result to write is below the
lower limit value.
|
The value to write was out of range. Please
change the setting to write an in-range value.
|
|
RYAA025
|
The operation result to write is beyond the
upper limit value.
|
The value to write was out of range. Please
change the setting to write an in-range value.
|
|
RYAA026
|
Could not send processing request to the
network destination due to insufficient memory.
|
Close the other application programs or restart
the OS.
|
|
RYAA027
|
The specified group was not found.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA028
|
The two compared access tickets differ in their
nodes, equipment, or devices.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA029
|
The specified access ticket is not for this
node.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA030
|
Could not register the cache because of
insufficient memory.
|
Close the other application programs or restart
the OS.
|
|
RYAA032
|
The access ticket you tried to use in block
access is not of the block type.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA033
|
The small service to process was not found.
|
A fatal error occurred. Run transfer again.
Or, use GP-Pro EX to run forced transfer. Then
transfer again.
|
|
RYAA034
|
The size of block access to the device exceeded
the limit.
|
The max buffer size for Device Block Write/Read
is 10KB. Please set a size less than that.
|
|
RYAA035
|
A different network project is being used.
|
Please transfer the project file with GP-Pro EX
again.
|
|
RYAA037
|
The no. of requests/the buffer size of requests
to Read/Write via network at a time exceeded the limit( **** ).
|
Please recheck the settings of requests from
and GP-Pro EX to the network destination, and redesign the system
to limit the no. of requests to the max value.
|
|
RYAA048
|
A communication error occurred during
communication with the destination node. Please confirm that the
network connection to the node has been properly established.
|
Check that the network and cables between this
display unit and the target unit are properly established and
connected.
|
|
RYAA049
|
The destination node did not responded within
the specified time. Please confirm that the network connection to
the node has been properly established.
|
The response from the client is not within the
timeout period set for the client.
|
|
RYAA050
|
The destination node did not responded within
the specified time. Please confirm that the network connection to
the node has been properly established.
|
The response from the server is not within the
timeout period set for the server.
|
|
RYAA051
|
Communication with the destination Node stopped
because the destination or local Node closed.
|
Please go into online mode with the connected
display unit.
|
|
RYAA064
|
Failed to read the device.
|
The data may have been read into an illegal or
undefined device address. Please specify a proper device
address.
|
|
RYAA065
|
Failed to write the device.
|
The data may have been written into an illegal
or undefined device address. Please specify a proper device
address.
|
|
RYAA069
|
The specified request is not supported.
|
Please upgrade GP-Pro EX to a supported version
by transferring the system.
|
|
RYAA070
|
The specified request is not supported.
|
Please upgrade GP-Pro EX to a supported version
by transferring the system.
|
|
RYAA080
|
The project ID of the network project file is
different. (A different network project is being used.
|
Please transfer the project file with GP-Pro EX
again.
|
|
RYAA081
|
The network project file does not have
necessary data.
|
Please transfer the project file with GP-Pro EX
again.
|
|
RYAA082
|
The network project file is damaged.
|
Please transfer the project file with GP-Pro EX
again. If it not enough, please transfer the project file with
GP-Pro EX again.
|
|
RYAA083
|
The network project file does not exist.
|
Please transfer the project file with GP-Pro EX
again. If it not enough, please transfer the project file with
GP-Pro EX again.
|
|
RYAA090
|
Unable to connect to server. Exceeding client
limit.
|
Terminate GP-Viewer EX that has been connected
and try the connection again.
|
|
RYAA091
|
Unable to connect to server. Server settings
have changed.
|
Try connecting to the server again.
|
|
RYAA092
|
Unable to connect to server. Server
authentication failed.
|
Try connecting to the server again.
|
|
RYAA093
|
Unable to connect to server. Server is starting
up.
|
Try connecting to the server again.
|
|
RYAA096
|
Failed to transfer data to display
unit.(****)
|
Please confirm that the PLC connected to the
display unit works properly. Or please transfer the project file
with GP-Pro EX again.
|
|
RYAA097
|
Failed to read the device from display
unit.
(****)
|
Accessed an read-protect area. Please change
the setting to avoid this.
|
|
RYAA098
|
Failed to write the device to display unit.
(****)
|
Accessed an write-protect area. Please change
the setting to avoid this.
|
|
RYAA099
|
In device access to the display unit, the
device number was out of range.
|
An invalid device was specified. You are
accessing a device which does not exist.
|
|
RYAA100
|
Failed to transfer data to display unit. (The
destination Node does not respond.))
|
The Destination Node does not respond. Check
the following:
-
The network cable is properly connected.
-
The destination node is ON.
-
The IP address is correct.
Or please transfer the project file with GP-Pro
EX again.
|
|
RYAA101
|
Failed to read the device from display
unit.
(The Destination Node does not respond.)
|
The Destination Node does not respond. Check
the following:
-
The network cable is properly connected.
-
The destination node is ON.
-
The IP address is correct.
|
|
RYAA102
|
Failed to write the device to display unit.
(The destination Node does not respond.))
|
The Destination Node does not respond. Check
the following:
-
The network cable is properly connected.
-
The destination node is ON.
-
The IP address is correct.
|
|
RYAA103
|
Operation was interrupted because the display
unit was not online anymore.
|
The process was interrupted because the display
unit was not online anymore. to complete the process, set the
display unit online and repeat the process.
|
|
RYAA112
|
Failed to update SRAM data.
|
Forcibly transfer the system using GP-Pro
EX.
|
|
RYAA113
|
No accessing SRAM while processing.
|
Forcibly transfer the system using GP-Pro
EX.
|
|
RYAA114
|
Unsupported request was set when accessing
SRAM.
|
Forcibly transfer the system using GP-Pro
EX.
|
|
RYAA115
|
Could not retrieve SRAM data because of
insufficient memory.
|
Close the other application programs or restart
the OS.
|
|
RYAA116
|
Could not register periodical SRAM update
because of insufficient memory.
|
Close the other application programs or restart
the OS.
|
|
RYAA125
|
Screen changes are not permitted from the
client.
|
The screen switch request was rejected. Check
the following:
-
Screen switch from the client is enabled.
-
Writing GP-Viewer data is not disabled.
-
The forced screen switch flag of the server is
set to OFF.
|