T.5.3 FLEX NETWORK analog unit, 2ch analog unit will not
operate
Is an error code displayed?
Cause
FLEX NETWORK unit settings may be incorrect.
Solution
Check the error code. See the following sections for the
description and handling method of the error code.
T.8 Errors displayed with an expansion
unit
See the following sections for the
description and handling method of the error code.
Can the device connected to the FLEX NETWORK board perform input
and output functions normally?
Check whether the device connected to the FLEX NETWORK board
performs input/output operations properly in order to determine
whether the problem is in the GP or not.
When an analog unit (Example: FN-AD02AH) is
used
-
Go to offline mode and touch [Peripheral Settings] on the item
changeover switch.
-
[Peripheral
Settings] screen opens. Touch [I/O Driver] and then [FLEX NETWORK Driver].
-
[I/O
Driver] screen opens. Touch [I/O Monitor].
-
[I/O
Monitor] screen opens. Set the [Transmission Speed], [S-No.], and [Model].
-
Touch this switch to go to the next screen and set
[CH] (channel) and
[Range].
-
The input monitor screen is displayed. The input
status is indicated with an integer value.
-
When the connection device is
operating normally
When the connection device is operating
normally, check the following GP-Pro EX settings because there is
no problem with the Display side and the unit side:
-
Check if the correct unit is selected in [Unit] in
[I/O Driver Setting] in the [System Settings].
31.4.1 Procedure - Using
FLEXNETWORK External I/O
-
Check if [Run at Start Up] is set to [Run] in
offline mode or in GP-Pro EX.
5.3.5 System
Settings [Display Unit] - [Logic] Settings Guide
M.19.1 [Home] Setting
Guide
-
Check if [Logic Programs] in [System Settings] is
set to [Enable] in offline mode or in GP-Pro EX.
5.3.5 System
Settings [Display Unit] - [Logic] Settings Guide
-
When the connection device is not
operating normally
When the connection device is not operating
normally, check the wiring of the Display and connected device and
then the following items:
Check if the cable is functioning normally by
performing a communication check.
Check whether the FLEX NETWORK unit connected to the FLEX
NETWORK board can communicate properly.
-
Go to offline mode and touch [Peripheral Settings] on the item
changeover switch.
-
[Peripheral
Settings] screen opens. Touch [I/O Driver] and then [FLEX NETWORK Driver].
-
[I/O
Driver] screen opens. Touch [Check Comm].
-
[Start]. Touch the button.
-
The communication check screen will display. When
no problem is found with the communication, the total number of
units that communicated successfully and the S-No assigned to the
units are highlighted. If communication is successful, please check
whether the device connected to the FLEX NETWORK unit operates
properly or the cable is correct.
If communication fails, check the communication cable for breaks,
the power supply of the unit, and the termination resistor of the
unit. If the problem continues, the I/O unit or display unit may be
faulty. Please contact the Pro-face customer care
center.
T.11.2 Telephone
Contact
* The following list shows the I/O units supported by the
communication check. (Example: When setting FN-X16TS(1),1 S-No.1
and FN-XY32SKS (4),1,S-No.2, S-no.1 to 5 are highlighted on the
screen above.
Type
|
Model
|
Number of stations
|
DIO
|
FN-X16TS
|
1
|
FN-X32TS
|
2
|
FN-Y08RL
|
1
|
FN-Y16SK
|
1
|
FN-Y16SC
|
1
|
FN-XY08TS
|
1
|
FN-XY16SK
|
1
|
FN-XY16SC
|
1
|
FN-XY32SKS
|
4
|
Analog
|
FN-AD02AH
|
1
|
FN-AD04AH
|
4
|
FN-DA02AH
|
1
|
FN-DA04AH
|
4
|
High Speed Counter Unit
|
FN-HC10SK
|
8
|
Single-Axis Positioning Unit
|
FN-PC10SK
|
4
|
|