Error No.
|
ID/No./Rung
|
Error Message
|
Solution
|
Reference
|
1000
|
Peripheral device settings
|
Ports settings are duplicated. Check the
Peripheral List.
|
Check the peripheral device identified with the
icon and change to a unique port
number.
|
7.2.1 Procedure -
Connecting to Multiple Device/PLCs
|
1001
|
Security
|
The security password already exists. Please
change the password.
|
Please set a different password for each
level.
|
23.9.1.1 Password
Settings
|
1002
|
Alarm Settings
|
Exceeded data history limit. The display can
use up to 768 records.
|
Reduce the number of stored history events to
768 items or less.
|
20.10.1 Common Settings
(Alarm) Setting Guide
|
1003
|
Alarm Settings
|
The number of messages that can be saved has
been exceeded. The display unit can use up to 2048 messages
counting all the Bit Monitoring and Word Monitoring blocks.
|
Delete excess messages so that the number of
alarm messages does not exceed 2048 items.
|
20.10.1.2
Alarm Settings (Block 1) - Bit Monitoring
20.10.1.3
Alarm Settings (Block 1) - Word Monitoring
|
1004
|
Alarm Settings
|
The maximum number of Word Monitoring messages
has been exceeded for this display unit. The maximum number in Word
Monitoring is 768.
|
Delete excess messages so that the number of
word monitoring alarm messages does not exceed 768 items.
|
20.10.1 Common Settings
(Alarm) Setting Guide
|
1006
|
Video/Movie Settings
|
The video/movie parts cannot be used with the
selected display unit. Please remove these parts from the
project.
|
Delete [Video/Movie Settings].
|
1.5 Supported
Features
|
1007
|
FTP Server Settings
|
The FTP Server settings cannot be used with the
selected display unit. Please remove these settings from the
project.
|
Delete [FTP Server Settings].
|
28.10.2 FTP Server
Settings Guide
|
1008
|
Sound Settings
|
Sound data cannot be used with the selected
display unit. Please remove the sound data from the project.
|
Delete sound data.
|
1.5 Supported
Features
|
1009
|
Image Unit Window
|
The Image Unit Window cannot be used with the
selected display unit. Delete the Image Unit Window.
|
Delete the Image Unit Window.
|
1010
|
—
|
The display unit can use up to 1,000 variables.
Please check the settings in the Symbol Variable list.
|
Delete excess variables so that the number of
variables does not exceed 1000 items.
|
8.14.5 Common Settings [Symbol
Variables] Settings Guide
|
1011
|
Alarm Settings
|
When Use same address is selected, alarm
registration is required in the first row.
|
If [Address n (1 to 8):Use Same Address] of
[Acquire Data in Each Alarm Registration] in Alarm Settings is ON,
you must always set the alarm in the first line. Set the alarm in
the first line of the target alarm block.
|
20.10.1.2
Alarm Settings (Block 1) - Bit Monitoring
|
1012
|
Security
|
There are no Users. Please add Users.
|
There are blank user IDs in [User ID] of
Security Settings. Set all user IDs with up to 8 single-byte
characters.
|
23.9.1 Common
(Security Settings) Settings Guide
|
1013
|
Security
|
There are no passwords set up. Please add
passwords.
|
There are blank passwords in [Password] of
Security Settings. Set all passwords with up to 8 single-byte
characters.
Alternately, clear [Add User ID] to move to password mode.
|
23.9.1 Common
(Security Settings) Settings Guide
|
1014
|
Security
|
User ID already exists. Please enter User
ID.
|
There are duplicate user IDs in [User ID] of
Security Settings. Modify User ID Settings to avoid duplicate user
IDs.
|
23.9.1 Common
(Security Settings) Settings Guide
|
1017
|
Alarm Settings
|
You cannot use the Device/PLC banner message
display and Alarm banner simultaneously.
|
Both [Use Memory Link Flow Message Display] in
Device/PLC Settings and [Use Flow Display] in Alarm Settings are
set. You cannot use these two settings simultaneously. Set the
[Flow Display] function of Device/PLC Settings or Alarm Settings to
OFF.
|
20.10.1 Common Settings
(Alarm) Setting Guide
|
1018
|
Main Unit - Remote Viewer Settings
|
The current model does not support the Remote
Viewer Settings - Web Server.
|
Web Server works only on GP models that support
network connections.
Uncheck [Enable Web Server] and check the
selected display model.
|
1.5 Supported
Features
|
1019
|
Main Unit - Remote Viewer Settings
|
The current model does not support the Remote
Viewer Settings - FTP.
|
FTP works only on GP models that support
network connections.
Uncheck [Enable FTP] and check the selected
display model.
|
1020
|
Alarm Settings
|
The font defined in the printer settings is not
supported. The defined language supports Stroke Fonts only.
|
This error appears when the defined alarm
language and alarm print settings do not support the font defined
in the print format settings. Please use supported fonts.
[Standard Font] supports [ASCII], [Japanese],
Chinese Simplified] and [Korean] in [Print Format Settings]. For
the other languages, please select [Stroke Font].
|
20.10.1.1 Alarm Guide
|
1021
|
Extended Settings
|
Ethernet Multilink cannot be used with the
current device/PLC settings.
|
In [Device/PLC], select a PLC that supports
Ethernet Multilink.
|
7.9.2 Restrictions When
Connected to Multiple Display Units (Ethernet Multilink
Settings)
|
1022
|
*1
|
Unable to indirectly specify the upper/lower
limits for sampling data with the current model. Please remove the
indirect specification of sampling data.
|
The indirect specification of the upper/lower
limits is not supported by the LT series and GP-3300 series Rev 3
or earlier. Change to the supported unit model or do not use the
indirect specification of the upper/lower limits for sampling
data.
|
5.3.14 System Settings
[Device/PLC] Settings Guide
|
1023
|
Mode
|
Unable to use Bulletin Messages with the
current model. Please delete the Bulletin Message.
|
Bulletin Messages cannot be used with the LT
series. Change to the supported model or uncheck [Enable Bulletin
Messages].
|
17.6.3 Message Display
[Bulletin Message] Settings Guide
|
1024
|
Extended Settings
|
Unable to use Ethernet Multilink with the
current model. Please remove Ethernet Multilink.
|
Ethernet Multilink cannot be used with the
specified model. Change to the supported model or uncheck [Enable
Ethernet Multilink].
|
1.5 Supported
Features
|
1025
|
*1
|
Unable to use Bulletin Messages with the
current model. Please delete the Bulletin Message.
|
Bulletin Messages cannot be used with the LT
series. Change to the supported model or delete the Bulletin
Message(s).
|
17.6.3 Message Display
[Bulletin Message] Settings Guide
|
1026
|
Device/PLC Settings
|
Exceeding 32 devices set up on a single driver.
Please check if all the devices are required.
|
Assign devices so that one driver has 32 or
less nodes for all ports.
|
5.3.14 System Settings
[Device/PLC] Settings Guide
|
1027
|
Alarm Settings
|
Unable to use extended alarms with this model.
Please remove extended alarms.
|
Change to a display unit model that supports
the feature, or from the [Common Settings] click [Alarm] and in the
[Alarm Type] property select the [Basic] option.
|
20.10.1 Common Settings
(Alarm) Setting Guide
1.5 Supported
Features
|
1028
|
Alarm Settings
|
*** addresses are being used. This display unit
supports up to "n" addresses, including bit and word monitored
addresses in all blocks.
|
Make the total number of all block, bit, and
word addresses n or less. (n is the maximum number of addresses
supported by the model you are using.)
|
—
|
1029
|
Text Table
|
Unable to expand the number of text table
indexes with this model.
Please remove the expanded text table
indexes.
|
Change to a display unit model that supports
the feature, or from the [Common Settings] click [Text Table] then
clear the [Expand index count] check box.
|
18.7.1.1 Text
Table
1.5 Supported
Features
|
1030
|
—
|
The amount of Function Expansion Memory used
exceeds the maximum limit.
Please check the Function Expansion Memory
settings.
|
Adjust the total size of the extended alarm
data and text table data so it is less than the memory remaining
after the reserved area is deducted from the 8 MB.
You can check the Function Expansion Memory
settings for a project file on the [Project Information] dialog
box.
|
3.7.2.3
Project Information - Send Data
|
1031
|
Display Unit - Extended Settings
|
Unable to use Function Expansion Memory with
this model. Please set None to Function Expansion Memory.
|
Change to a display unit model that supports
the feature, or from the [System Settings] click [Display Unit] and
in the [Extended Settings] tab's [Function Expansion Memory] list
select [None].
|
5.3.7 System
Settings [Display Unit] - [Extended] Settings Guide
1.5 Supported
Features
|
1032
|
Printer Settings
|
Unable to use * with this model.
Please change the printer type.
|
Change to a display unit model that supports
the feature or specify a printer that does not match any of the
following.
|
35.6.2 Printer
Settings Guide
|
1033
|
Extended Settings
|
Unable to draw using standard fonts on this
model.
Please remove draw using standard font.
|
Change to a display unit model that supports
the feature, or from the [System Settings] click [Display Unit],
and in the [Extended Settings] tab's [Compatibility] dialog box
clear the [Draw Using Standard Font] check box.
|
5.3.7 System
Settings [Display Unit] - [Extended] Settings Guide
1.5 Supported
Features
|
1034
|
Text Table
|
To use [Synchronize Text Display language with
Text Table], in the Text Table first select the [Enable Language
Change Feature] check box.
|
Check the [Enable Language Change Feature]
checkbox.
|
18.7.1.2 Language
Change
|
1035
|
Alarm Settings
|
The selected model does not support multiple
line alarm printing or storage. Please set the multiple line
setting OFF.
|
For the common (alarm) settings, remove the
check marks next to [Multiple Line Message Printing] and [Multiple
Line Message Output (Save Alarm to CSV)].
|
20.10.1.1 Alarm Guide
|
1037
|
Operation Log Settings
|
The selected model does not support appending
values to the operation log.
|
Change to a display unit model that supports
the feature, or from the [Common Settings] click [Operation Log
Settings] then clear the [Append value to log] check box.
|
23.9.2 Operation Log
Settings
1.5 Supported
Features
|
1038
|
Display Unit - Display Settings
|
The selected model does not support Synchronize
Text Display language with the Text Table.
|
Change to a display unit model that supports
the feature, or from the [System Settings] click [Display Unit],
and in the [Display] tab clear the [Synchronize Text Display
language with Text Table] check box.
|
5.3.2 System Settings
[Display Unit] - [Display] Settings Guide
1.5 Supported
Features
|
1039
|
Clock Update Settings
|
Get From Device is invalid. Get From Device
setting in the Clock Update Settings.
|
Please adjust the [Get From Device]
setting.
|
5.4.1 Common - Clock
Update Settings
|
1040
|
User-Defined Functions
|
Circular reference in user-defined
functions.
|
Please remove the circular-reference in the
user-defined function.
|
22.9.2 User-Defined
Functions Settings Guide
|
1041
|
Clock Update Settings
|
This model does not support Clock Update
Settings. Turn off the Enable Clock Updates option.
|
Either remove the Clock Update
Settings or change models.
|
5.4.3 Common Settings -
Register Start Screen
|
1042
|
Register Start Screen
|
This model does not support the Register Start
Screen option. Disable the Register Start Screen option.
|
Either remove the Register
Start Screen or change models.
|
5.4.1 Common - Clock
Update Settings
|
1043
|
*1
|
This model does not support using an address to
define the sampling frequency.
Set the sampling frequency to a constant
value.
|
From the [Common Settings] select [Sampling],
in the [Mode] tab's [Sampling Frequency] area change [Frequency] to
[Constant].
|
25.8.3 Mode
|
1046
|
Alarm Settings
|
With this model, use the following date format
for alarms: yy/mm/dd.
|
In the [CSV Settings] area, change the [Date
Format] to [yy/mm/dd].
|
20.10.1.1 Alarm Guide
|
1047
|
*1
|
With this model, use the following date format
for sampling groups: yy/mm/dd.
|
In the [Display/Save in CSV] tab, change the
[CSV Date Format] to [yy/mm/dd].
|
25.8.4 Display/Save
in CSV
|
1049
|
Device/PLC Settings
|
The total number of Devices/PLCs has exceeded
64. Check the number of Devices/PLCs.
|
In the [System Settings] window's [Device/PLC],
assign devices so that one driver has 64 or less nodes for all
ports.
|
5.3.14 System Settings
[Device/PLC] Settings Guide
|
1050
|
Device/PLC Settings
|
Unable to use #MEMLINK for the Device ID
Address. Use another address.
|
In the [System Settings] window's [Device/PLC]
settings, use the LS area or USR area addresses for the [Device ID
Address] field.
|
5.3.14 System Settings
[Device/PLC] Settings Guide
|
1051
|
Device/PLC Settings
|
This model does not support Indirect Devices.
Remove Indirect Devices.
|
From the [System Settings] window's
[Device/PLC], remove the Indirect Device feature.
|
5.3.14 System Settings
[Device/PLC] Settings Guide
|
1052
|
Device/PLC Settings
|
Device ID is duplicated. Change the Device ID
in the Device/PLC settings.
|
From the [System Settings] window's
[Device/PLC], make sure indirect devices do not duplicate [Device
ID] values.
|
5.3.14 System Settings
[Device/PLC] Settings Guide
|
1053
|
Device/PLC Settings
|
The selected Device/PLC is not supported when
the Enable Ethernet Multilink option is off. Change the
Device/PLC.
|
From the [System Settings] window's
[Device/PLC], change the device/PLC.
|
5.3.14 System Settings
[Device/PLC] Settings Guide
|
1054
|
Device/PLC Settings
|
The total number of Devices/PLCs exceeds the
maximum limit. Remove selected Devices/PLCs.
|
From the [System Settings] window's
[Device/PLC], delete the device/PLC.
|
5.3.14 System Settings
[Device/PLC] Settings Guide
|
1055
|
Device/PLC Settings
|
Device ID is duplicated. Change the Device ID
in the Device/PLC settings.
|
From the [System Settings] window's
[Device/PLC], do not duplicate [Device ID] values within the same
driver.
|
7.8.1 System Settings
[Device/PLC] Settings Guide
|
1101
|
*1
|
Data Display's device/PLC settings are
unreferenced. Please reference a valid device/PLC.
|
In a Data Display (Numeric Display/Text
Display), in the [Basic] tab with the [Extended] settings, the
[Address Type] is set to [Device Type Address] but the [Monitor
Word Address] area's [Device/PLC] property is empty. Please set up
a valid device/PLC.
|
14.11.1.2
Numeric Display - Basic Settings/Extended
|
1102
|
*1
|
One screen can have one Data Display (Input
Display).
|
Limit the number of Data Display devices to
only one per screen.
|
—
|
1103
|
Keypad
|
Keypad supports only Data Display parts (Show
Limit Value/Input Display).
|
Do not place a Data Display on the keypad
unless it is showing Show Limit Value or Input Display.
|
—
|
1104
|
Keypad
|
One keyboard can have one Data Display (Show
Limit Value).
|
You can place only one Data Display (Show Limit
Value) on the keypad.
|
—
|
1105
|
*1
|
Cannot use animation with this model. Please
remove animation.
|
Change the model or remove the animation
setting.
|
1.5 Supported
Features
|
1106
|
*1
|
A group set up with animation includes a Data
Display using the Display Input feature.
|
Change the setting of the Data Display that is
using the Display Input feature.
|
—
|
1108
|
*1
|
This model does not support the use of image
fonts with Selector Lists, Data Displays, Alarms, Text Alarms or
Message Displays (Text Display).
Please change the font type.
|
Change the font type to something other than
bitmap fonts.
|
—
|
1109
|
*1
|
Unable to use bitmap fonts with this model.
Please change fonts.
|
Change the font type to something other than
picture fonts.
|
—
|
1110
|
*1
|
This model does not support the use of image
fonts in the text table with text, labels, and message
displays.
Please either change the font type, or input
text directly.
|
Please either change the font to something
other than image fonts, or enter the text directly.
|
—
|
1111
|
Symbol Variable Settings
|
Symbols * and higher exceed the usable address
range.
|
[Bit Address] or [Word Address] setting in a
symbol variable, set up as an array, exceeds the device address
range. Please change the array elements so the array elements are
inside the device address range (up to *).
|
8.14.5 Common Settings [Symbol
Variables] Settings Guide
|
1112
|
*1
|
This model is unable to use anti-aliasing with
image fonts.
|
Clear the [Anti-alias] check box.
|
—
|
1200
|
*1
|
Unable to use a XY Historical Scatter Graph
with the current model. Please delete the XY Historical Scatter
Graph.
|
The XY Historical Scatter Graph cannot be used
with the LT series and the GP-3300 series Rev 3 or earlier. Change
the model or remove the XY Historical Scatter Graph.
|
—
|
1201
|
*1
|
Unable to use a XY Block Display Scatter Graph
with the current model. Please delete the XY Block Display Scatter
Graph.
|
The specified model cannot use this feature.
Change the model or remove the XY Block Display Scatter Graph.
|
1.5 Supported
Features
|
1202
|
*1
|
Cannot use Selector List with this model.
Please delete the Selector List.
|
The Selector List cannot be used with the LT
series and the GP-3300 series Rev 3 or earlier. Change to the
supported model or remove the Selector List Part.
|
—
|
1203
|
*1
|
Unable to define block addresses in alarm parts
with this model.
Please change block addresses to direct
addresses in the alarm parts.
|
Change to a display unit model that supports
the feature, or in the [Alarm] dialog box's [Basic] tab set [Block]
to [Direct].
|
20.10.2 Alarm Parts Settings
Guide
1.5 Supported
Features
|
1204
|
*1
|
Unable to set up object data (CF<-->FTP
or USB storage<-->FTP) on this model.
Please change the object data.
|
Change to a display unit model that supports
the feature, or open the [Special Data Display] [File Manager]
dialog box and set the [Basic] tab's [Target Data] to any option
except items associated with FTP.
|
26.9.3.1 File Manager -
Basic
1.5 Supported
Features
|
1205
|
*1
|
Unable to sort by date on this model.
Please disable sorting by date.
|
Change to a display unit model that supports
the feature, or open the [Special Data Display] [File Manager]
dialog box and clear the [Extended] tab's [Sort By Date] check
box.
|
26.9.3.2 File Manager
- Extended
1.5 Supported
Features
|
1206
|
*1
|
Unable to use the default path with this
model.
Please disable the default path.
|
Change to a display unit model that supports
the feature, or open the [Special Data Display] [File Manager]
dialog box and clear the [Extended] tab's [Default Path] check
box.
|
26.9.3.2 File Manager
- Extended
1.5 Supported
Features
|
1207
|
*1
|
The selected model does not support multiple
line alarm displays. Please set the Message Display Method to
1.
|
For the alarm part, select [Basic] and then
[Display Format]. Next, change [Message Display Method] to [1 line
display].
|
20.10.2 Alarm Parts Settings
Guide
|
1209
|
*1
|
This model cannot use Image Sensor Displays.
Please remove the Image Sensor Display.
|
Delete the Image Sensor
Display from the project.
|
—
|
1210
|
*1
|
The Image Sensor Display camera is undefined.
Select a valid camera.
|
From the [Image Sensor Display] dialog box's
[Select camera] field define the connected equipment.
|
28.10.10
Image Sensor Display Settings Guide
|
1211
|
*1
|
This model does not support the use of
Operation Locks in Special Switches. Remove the Operation Lock
operation from the Special Switch.
|
Remove the Operation
Lock from the project.
|
10.15.4.1 Special
Switch - Switch Features
|
1213
|
—
|
This model cannot use Image Sensor Displays.
Please remove the Image Sensor Display.
|
Please remove the Image Sensor Display.
|
28.11.3 Image Sensor
Display Restrictions
|
1500
|
Project Information
|
The transmission data size exceeds the maximum
limit. Check your settings.
|
Set the User Screen Area within the following
memory ranges for each model.
GP-3300 Series (6 MB)
GP-3400 Series to GP-3700 Series (8 MB)
IPC Series (16 MB)
(There is a chance that 90% or more of the
memory will cause an error output because of the data
structure.)
|
6.5 Font Settings Guide
|
1501
|
—
|
*** Illegal address. Define a correct
address.
|
Input an address for the specified location
address with a keypad. ( *** indicates where the problem is
located, such as in common setting features or screens, such as
[Base screen 1].)
|
14.2.1
Procedure - Displaying/Inputting Numeric Data
|
1502
|
Symbol Variable Settings
|
There is a symbol without a device address.
Check the symbols in the Symbol Settings.
|
Delete the parts using a symbol for the address
settings or with no address settings, or set the address to parts
with no address settings.
|
8.8.2 Procedure -
Confirming Symbol Registration
|
1503
|
Font
|
The specified font has not been registered in
[Fonts for Projects]. Add it, in [Font Settings], or change the
font.
|
Add the font using [Font Settings] in the
system settings or change the font.
|
6.5 Font Settings Guide
|
1504
|
Project
Information
|
Exceeded
backup memory (SRAM) capacity. Excess data is not saved. Check the
Project Information.
|
Set up the project so you do not exceed the
display unit's backup memory capacity. You can check the capacity
in the [Project Information] dialog box's [SRAM Information].
|
3.6 Viewing
Project Information
|
1505
|
Sampling Settings
|
The group,
where Sampling settings has the Retain Sampling Data (SRAM) option
turned off, exceeds the data save area. Excess data is not
saved.
|
The sampling group with the [Retain Sampling
Data (SRAM)] check box cleared, exceeds the data storage area.
Reduce the sampling words or the number of
sampling times so that the setting remains within the range of the
data storage area.
|
25.11.1 Usage Capacity of
Sampled Data
|
1506
|
—
|
The project contains features that require a CF
Card. However, the selected display does not support CF cards so
these features will not run.
|
The GP3202B model supports the CF card export
folder. Change the model or do not set the CF card output
folder.
|
5.3.1 System Settings
[Display] Settings Guide
3.6 Viewing
Project Information
|
1507
|
Global
D-Script
|
The number of devices limit has been exceeded.
The total number of allowable devices in the all Global Scripts is
255.
|
Make sure the total number of addresses to use
in Global D-Scripts (including calling functions) does not exceed
256 by creating multiple scripts with the same tri |