Error No.
|
Error Message
|
Cause and Solution
|
Reference
|
RAAA001
|
No project data exists. (Transfer a
project.)
|
No project file exists.
Transfer a project.
|
34.2.1 USB Transfer -
Transferring from Computer to Display Unit (Send)
34.3.1 Transfer
- Transferring from Computer to Display Unit (Send)
|
RAAA002
|
The project data size exceeds the capacity.
|
The project data size exceeds the maximum
capacity*. Or, the number of screens exceeds 16,000
files. Reference the GP-Pro EX Project Information, and make sure
it does not exceed the general capacity.
* The maximum capacity of the project data size
varies depending on the Display model. (Example: 8 MB for
GP-3500T).
|
3.6 Viewing
Project Information
|
RAAA003
|
The project data is invalid. (Transfer the
project again.)
|
There is an error in the project file.
Transfer the project again.
|
34.2.1 USB Transfer -
Transferring from Computer to Display Unit (Send)
34.3.1 Transfer
- Transferring from Computer to Display Unit (Send)
|
RAAA004
|
The system screen is invalid. (Execute forced
transfer.)
|
The system screen does not exist or is
invalid.
Force a transfer.
|
34.11.1 Transfer
Settings Guide
|
RAAA005
|
The specified initial screen number does not
exist.
|
The screen cannot display because the screen
number designated in the Initial Screen Settings does not exist in
the project. Change the initial screen number or add the screen.
The screen number designated in the parentheses is displayed.
|
5.3.2.2 Display
Unit [Display] - Display Settings
|
RAAA006
|
Project contains unsupported functions and
cannot be displayed.
|
The current model includes functions which the
runtime program cannot recognize. Please remove the unsupported
function and transfer again.
The editor and runtime versions may not match.
Update the runtime version.
|
—
|
RAAA007
|
The no. of parts in the screen exceeds the
limit. (MAX 384)
|
There are more than 384 parts set on a single
screen.
The number of parts exceeds the limit during a
screen change or when opening a window. Make sure to set parts
within the permitted range.
|
3.8.1 Restrictions
for Screen Display
|
RAAA008
|
The font ( **** ) does not exist. (Transfer the
font with the project.)
|
The font you are trying to display does not
exist in the system. Download the font into the system.
The following table shows the font names.
Japanese Standard
|
English Standard
|
Korean Standard
|
Chinese (Simplified Character) Standard
|
Chinese (Traditional Character) Standard
|
Japanese Stroke
|
English Stroke
|
Korean Stroke
|
Chinese (Simplified Character) Stroke
|
Chinese (Traditional Character) Stroke
|
Cyrillic Alphabet Stroke
|
Thai Stroke
|
|
6.5 Font Settings Guide
|
RAAA010
|
The CF card has not been inserted, or the CF
card hatch is open.
|
The CF card cannot be accessed. Check if the CF
card is inserted or if the CF hatch can close. Insert the CF card
and close the hatch.
|
GP3000 Series Hardware Manual
|
RAAA011
|
Failed to start from the CF card.
|
Regardless of whether DIP SW1 is ON, the
necessary file does not exist to start from the CF card. Or the
necessary file may have an error. Copy the startup project to the
CF card again.
If the access to the CF card has been disabled
intentionally, check the following. Previous settings may still
remain.
-
Select [Display Unit] - [Operation Settings] -
[Memory Card Settings] and check the [Screen Capture] settings.
-
Select [Common Settings] - [Sampling] and check
[Display/Save in CSV] for each registered sampling.
-
CF file write function of the D-Script
-
Select [Common Settings] - [Operation Log Settings]
and check the settings.
|
—
|
RAAA012
|
The project data contains functions that are
not supported by this model.
|
When running on display unit:
The current model includes functions which the
runtime program cannot recognize. Change to a model that supports
the feature or remove it.
Please refer to the following for supported
features.
1.5 Supported
Features
When running simulation:
Simulation does not support all features. You
can only simulate supported features.
Please refer to the following for unsupported
features.
33.7.1 Restrictions on
Simulation
|
RAAA013
|
USB storage location not found.
|
The USB storage device cannot be accessed due
to the poor connection or recognition problem. Check if the USB
storage device is connected. If connected, disconnect and then
reconnect the USB storage device.
|
RAAA014
|
Failed to start from USB storage.
|
The file required for startup from the USB
storage device does not exist. Or the necessary file may have an
error.
Check that the startup file "boot.cfg" and the
"pj001" folder are located directly under the USB storage.
|
RAAA015
|
Unable to go off-line.
|
Offline mode files do not exist, or are
damaged. Please run a forced transfer.
|
RAAA016
|
Bitmap font unavailable. (Please transfer a
project with this font.)
|
You are using a font that is not registered in
the [Image Font] settings. Add fonts used in the project, and
transfer again.
|
RAAA017
|
Unable to use CF card. Its capacity level is
unsupported.
|
External storage has been formatted in a format
not supported. If external storage with capacity over 2GB has been
formatted as FAT16, reformat as FAT32.
|
RAAA018
|
Unable to use USB storage. Its capacity level
is unsupported.
|
RAAA019
|
Because the image font is set, it is not
possible to display it.
|
When using [Synchronize with Text Table], the
Data Display (Text Display) cannot use image fonts. Please change
to Standard Font or Stroke Font.
|
RAAA050
|
Clock
Setting Error
|
When changing the clock data, the data write to
the clock IC failed.
The IC chip may be broken.
Set up value is invalid as clock data. Please
specify proper clock data.
|
RAAA051
|
Low battery
|
Due to low
voltage of the backup battery, data in the backup memory (SRAM) is
erased, and the clock data is not saved.
Supply
enough power to the display unit and set the clock data again. The
battery requires 24 hours of charging to reach a level that allows
backup operation, and about 96 hours (4 days) to be fully
charged.
|
GP3000 Series Hardware Manual
|
RAAA052
|
There is a problem with the hardware.
|
(****) indicates where the problem is in the
Display.
For example, when an error occurred with the
LAN port, "LAN" is displayed. This may be caused by a fault in the
display unit. Please contact the Pro-face customer care center.
|
—
|
RAAA060
|
Failed to save backup data
|
Failed to save backup data to internal memory.
Please run back up again. If this occurs frequently, the maximum
possible number of saves to internal memory may have been exceeded,
or the unit is damaged. Please contact the Pro-face customer care
center.
|
RAAA061
|
Failed to read backup data
|
There is a problem with the backup data saved
to internal memory. Previously, while saving the backup the power
may have been disconnected. Please run back up again. If this
occurs even though the backup is run again, the maximum possible
number of saves to internal memory may have been exceeded, or the
unit is damaged. Please contact the Pro-face customer care
center.
|
RAAA062
|
Unable to use backup data
|
Unable to save or read backup data in internal
memory. The maximum possible number of saves to internal memory may
have been exceeded, or the unit is damaged. Please contact the
Pro-face customer care center.
|
RAAA063
|
Failed to get clock data
|
Device/PLC is not supporting updating the
clock. Please check if the device/PLC supports clock updates.
|
5.4.1 Common - Clock
Update Settings
|
RAAA100
|
The system start device address is
incorrect.
|
The system device start address is not set
correctly or has an error.
Set the correct address while in offline mode,
or transfer a project.
|
5.3.6 System
Settings [Display Unit] - [System Area] Settings Guide
|
RAAA102
|
Failed to read from the Device/PLC.
|
Failed to read from the device/PLC.
Confirm the connection status, such as whether
the communication cable is disconnected, etc.
The part name is entered in the
parentheses.
|
GP3000 Series Hardware Manual
|
RAAA103
|
The specified address is incorrect.
|
The designated address is incorrect. Make sure
to set the correct address. The part name is entered in the
parentheses.
|
—
|
RAAA110
|
Remote PC Access error. Unable to recover.
|
An internal initialization error or system
error occurred.
Restart the display unit, or review the screen
settings.
|
M.15.1
System Menu - Offline, CF Startup, Error, Reset
|
RAAA111
|
Unable to certify Remote PC Access server.
|
The password is invalid.
Check if the password matches the password
specified on the Server PC.
|
36.3
Display or Operate a Computer from the Display Unit
|
RAAA112
|
Failed to connect to Remote PC Access
server.
|
No Server PC is found. Or failed to connect to
the server.
Check if the IP address matches with that for
the Server PC.
Check if the Server PC is active.
Check the settings on the Server PC.
Check if the Server PC Firewall is enabled.
|
RAAA113
|
Connecting to Remote PC Access server.
|
The previous disconnection process is not
completed.
Wait for a while (75 seconds maximum), and then
retry connecting to the server.
|
—
|
RAAA114
|
Missing Remote PC Access license key code.
Enter key code in offline mode.
|
With GP-Pro EX, the RPA function key code has
not been set up. Enter an RPA key code in offline mode.
|
M.5.3
Setting up GP-Viewer EX or Remote PC Access License
|
RAAA115
|
PC input is restricted.
|
[Touch Input Inhibition] is set in the RPA
window display. Disable the setting of [Touch Input
Inhibition].
|
36.4.1 Remote PC
Access Window Display Setting Guide
|
RAAA120
|
D-Script Error (The specified function does not
exist or the function has an error.)
|
The function called in the D-Script does not
exist. Or there is an error in the function. Check the command
format.
|
22.11 Built-In Function
(Instruction) / Conditional Expressions
|
RAAA121
|
D-Script Error (These functions are nested to
10 levels or more.)
|
Functions in the D-Script are nested to 10
levels or more.
Reduce the levels in the "if" and "loop"
structures.
* A nesting level is when function A calls
function B, and then again when function B calls function C
(function calling level).
|
22.11.10.3 loop -
endloop
|
RAAA122
|
D-Script Error (An expression exists, that is
not supported by this version.)
|
An incompatible function was found in the
project's D-Script. Update the runtime version.
|
—
|
RAAA123
|
D-Script Error
(The SIO operation function is used in a condition where no
Device/PLC has been set.)
|
SIO Operation functions are used in a D-Script
while the device/PLC settings are not set. Configure the device/PLC
settings.
|
5.3.17 System Settings
[Script I/O] Settings Guide
|
RAAA124
|
The D-Script has an error.
|
There is an error in the used D-Script. Check
the command format.
|
22.11 Built-In Function
(Instruction) / Conditional Expressions
|
RAAA130
|
Global D-Script Error. (The Total Number of
Global D-Scripts exceeds the maximum of 32.)
|
The total number of Global D-Scripts exceeds
the limit. The maximum number of Global D-Scripts available is 32
(each function also counts as one script).
|
22.10.1
D-Script/Global D-Script Restrictions
|
RAAA131
|
Global D-Script Error.
(The total number of devices exceeds the maximum of 255.)
|
The total of all devices in the Global D-Script
exceeds the limit of 255 devices. Reduce the number of used devices
by using the Memory Operation function, etc.
|
RAAA132
|
Global D-Script Error (The specified function
does not exist or the function has an error.)
|
The function called in the Global D-Script does
not exist. Or there is an error in the function. Check the command
format.
|
22.11 Built-In Function
(Instruction) / Conditional Expressions
|
RAAA133
|
Global D-Script Error (These functions are
nested to 10 levels or more.)
|
Functions in the Global D-Script are nested to
10 levels or more.
Reduce the levels in the "if" and "loop"
structures.
* A nesting level is when function A calls
function B, and then again when function B calls function C
(function calling level).
|
22.11.10.3 loop -
endloop
|
RAAA134
|
Global D-Script Error (An expression exists,
that is not supported by this version.)
|
An incompatible function was found in the
project's Global D-Script. Update the runtime version.
|
—
|
RAAA135
|
Global
D-Script Error (The SIO operation function is used in a condition
where no Device/PLC has been set.)
|
SIO Operation functions are used in a Global
D-Script while the device/PLC settings are not set. Configure the
device/PLC settings.
|
5.3.17 System Settings
[Script I/O] Settings Guide
|
RAAA136
|
The Global D-script has an error.
|
There is an error in the used Global D-Script.
Check the command format.
|
22.11 Built-In Function
(Instruction) / Conditional Expressions
|
RAAA140
|
Extended D-Script Error (The total number of
functions exceeds the max of 255.)
|
The total number of Extended Scripts exceeds
the limit. The maximum number of Extended Scripts is 255.
Reduce the number of scripts by combining two
scripts into one, etc.
|
22.10.2 Extended Script
Restrictions
|
RAAA141
|
Extended
D-Script Error (The specified function does not exist or the
function has an error.)
|
A function called in the Extended Script does
not exist. Or there is an error in the function. Check the command
format.
|
22.11 Built-In Function
(Instruction) / Conditional Expressions
|
RAAA142
|
Extended
D-Script Error (These functions are nested to 10 levels or
more.)
|
Functions in the Extended Script are nested to
10 levels or more.
Reduce the levels in the "if" and "loop"
structures.
* A nesting level is when function A calls
function B, and then again when function B calls function C
(function calling level).
|
22.11.10.3 loop -
endloop
|
RAAA143
|
Extended D-Script Error (An expression exists,
that is not supported by this version.)
|
An incompatible function was found in the
project's Extended Script. Update the runtime version.
|
—
|
RAAA144
|
Extended
D-Script Error (The SIO operation function is used in a condition
where no Device/PLC has been set.)
|
SIO Operation functions are used in a Extended
Script while the device/PLC settings are not set. Configure the
device/PLC settings.
|
5.3.17 System Settings
[Script I/O] Settings Guide
|
RAAA145
|
The Extended D-Script has an error.
|
There is an error in the used Extended Script.
Check the command format.
|
22.11 Built-In Function
(Instruction) / Conditional Expressions
|
RAAA150
|
Incorrect password.
|
The security feature's password input is
incorrect. Confirm that the input is correct (upper-case/lower-case
letters, and so on) and enter the password again.
|
|