10.16.4.1 Special Operation - Selector List Settings
Special Action
Select the Special action.
This is the same as the Switch attached to a
Window part which triggers the Window. Press the Switch and the
designated Window displays. Press it again and the Window
closes.
This is the same as the Switch that is
attached to the Alarm part. This creates a Switch to manage
(Acknowledge/Move/Clear) the displayed Alarm History.
Alarm
History Switch
This is the same as the Switch that is
attached to the Text Alarm part. Creates a Switch to show the
displayed Text Alarm's scroll or Sub Screen.
Text Alarm
Switch
This is the same as the Switch that is
attached to the Historical Trend Graph. Creates a Switch to display
and scroll through historical data.
Historical
Trend Graph Switch
This is the same as the Switch that is
attached to the Sampling Data Display part. Creates a Switch to
scroll through a Sampling Data Display.
Sampling
Data Display Switch
When multiple display units are connected to
one PLC via GP-Viewer EX or Ethernet, and you start working on a
display unit/GP-Viewer EX, operations from other display
units/GP-Viewer EX become disabled. Therefore, you can create an
operation switch to re-enable operations on the other display
units/GP-Viewer EX.
Operation
Lock
Create an operation switch to change password
during the online mode (communicating to the device/PLC).
Security
This is the same as the Switch that is
attached to the Special Data Display [Filing]. Creates a Switch to
transfer filing data, scroll through a Filing Display, etc.
File Item
Switch
This is the same as the Switch that is
attached to the Special Data Display [File Manager]. Creates a
Switch to display the File Manager on the screen.
This is the same as the Switch that is
attached to the Special Data Display [Data Transmission].
Creates a Switch to transfer CSV data, scroll
through a Data Transfer Display, etc.
Data
Transfer Switch
This is the same as the Switch that is
attached to the Special Data Display [Show CSV].
Creates a Switch to scroll through a CSV Display or print CSV
data.
Switch
for CSV Display
This is the same as the switch attached to
the movie player. Create the switch to operate the screen for movie
playback.
Movie
Player Switch
Create a switch to display the Device monitor
and the Ladder monitor on the screen.
Start
Monitor Switch
Create a switch to directly specify and start
the application executable file when using WinGP. You can specify
settings such as the startup parameters and the watch on multiplex
start.
Start
Application
Create a switch to exit WinGP.
Exit
WinGP
Create a switch to reset the Display.
Create a switch to transfer to offline mode
(no communication with the device/PLC) for the Display.
This is the same as the switch attached to
the Remote PC Access Window Display. Display the RPA Window Screens
on the screen.
36.3
Display or Operate a Computer from the Display Unit
Creates a switch for transferring device/PLC
data stored on the display unit's CF card or USB storage. Touch the
switch to display the [Transfer Device/PLC Data] screen and
transfer the ladder file on the CF card or USB storage.
-
To prevent mistakes and unauthorized use, we
recommend setting up security on screens that have switches.
23.1 Settings Menu
-
Create the files for the Transfer Device/PLC
Data operation with the Data Copy Tool. For the list of drivers
that support the Data Copy Tool and information on transfer setup,
please see the "GP-Pro EX Device/PLC Connection Manual".
Window Parts ID
Set the ID of the Window to display when the switch is touched.
0 to 3833 is the set up range.
Alarm History Switch
Action
Select the alarm history switch operation: [Start], [End],
[Acknowledge], [Move], [Clear], [Sort], [Scroll], [Sub Display], or
[Alarm Number Acquisition Key].
Freeze Mode
When the [Action] is [Start], designate whether or not to use
Freeze Mode (stops the Alarm display in the current state and does
not perform updates).
Detail Action
When [Action] is selected as [Acknowledge], [Move], [Clear], or
[Sort], select the details.
Choose from [Acknowledge] or [Check All].
Choose from [Move Upward], [Move Downward],
[Scroll Up], or [Scroll Down].
Choose from [Clear], [Clear All], [Clear
Recovered Alarm], [Clear Acknowledged Alarm], [Clear All Recovered
Alarm], [Clear All Number of Occurrences Fields], [Clear Individual
Number of Occurrences Fields], [Clear All Accumulated Time Field]
or [Clear Individual Accumulated Time Field].
Choose from [Sort by Triggered Date and
Time], [Sort by Number of Occurrences], [Sort by Accumulated Time],
[Alarm Sort by Registration Order], [Sort by Level & Date and
Time], [Sort by Level & Number of Occurrences], or [Sort in
Reverse].
Select either [Scroll Right] or [Scroll
Left].
Number of Scroll Up/Scroll Down Moves
When [Detail Action] is [Scroll Up] or [Scroll Down], set the
number of moves the Switch will scroll when pressed once. The
setting range is from 1 to 768.
Get Operation Log
When [Action] is selected as [Acknowledge] or [Clear], specify
whether to get the operation log.
Text Alarm Switch
Action
Choose the action from [Move Upward], [Move Downward], [Scroll
Up], [Scroll Down], [Sub Display], or [End].
Number of Scroll Up/Scroll Down Moves
When [Action] is [Scroll Up] or [Scroll Down], set the number of
moves the Switch will scroll when pressed once. The setting range
is from 1 to 512.
Historical Trend Graph Switch
Action
Select the Display Historical Data switch operation for the
Historical Trend Graph: [Display Historical Data Switch], [Scroll
for Old Data], [Scroll for New Data], [Zoom Display], and [Zoom Out
Display].
Samples to Scroll
When [Action] is [Scroll for the Old Data] or [Scroll for New
Data], set the number of samples to scroll with one touch. The
setting range is from 1 to 65535.
Use only in Display Historical Data
When [Action] is selected as [Zoom Display] or [Zoom Out
Display], specify whether to use it only when displaying Historical
Data.
Historical Trend Graph Parts ID
When [Action] is selected as [Zoom Display] or [Zoom Out
Display], set the historical trend graph parts that reflect the
display condition.
Sampling Data Display Switch
Action
Choose the action from [Scroll Up], [Scroll Down], [Scroll
Left], or [Scroll Right].
Samples to Scroll
Set the number of samples to scroll when pressed once. The
setting range is 1 to 65,535 for [Scroll Up] and [Scroll Down], and
1 to 514 for [Scroll Left] and [Scroll Right].
Operation Lock
Action
Choose the action of operation lock switch from [Lock and
Unlock], [Lock] or [Unlock].
Do not automatically unlock
When selecting, the lock does not automatically unlock even
after the time set in [Time Out] in [Operation Lock Settings] in
the Display Unit [Extended Settings] has passed. to release, set
[Action] to [Lock and Unlock], or place a Special Switch for the
[Unlock] operation.
Security
Action
Choose the action of the set password switch: [Set Password],
[Log In] or [Log Off].
Setting Mode
When [Set Password] is the defined [Action], select [Overwrite]
or [Append].
Overwrite the password that was read-in to
the existing passwords.
Add the password that was read-in to the
existing passwords.
Load
Choose where to load the password from: [CF Card] or [USB
Storage].
After reflecting the password, delete the CSV
file.
After showing the password from the [Load] operation, specify
whether to delete the CSV file.
Log Off Screen
When selecting [Log Off] as the [Action], choose the log off
screen from [Start Screen], [Select Screen], or [No Screen
Movement].
When using [Select Screen], specify the
screen number to display when logging off.
Get Operation Log
Specifies whether to record the Operation Log.
File
Item Switch
Action
Choose the action of the switch in the Special Data Display
[Filing]: [Transfer from SRAM to Device/PLC], [Transfer from SRAM
to Internal Device], [Transfer from Device/PLC to SRAM], [Transfer
from Device/PLC to Internal Device], [Transfer from Internal Device
to SRAM], [Transfer from Internal Device to Device/PLC], [Move
Upward] or [Move Downward].
ID Number
Set the ID number of the Special Data Display [Filing] you want
to operate with the Special Switch. The value can be from 0 to
255.
Number of Moves
When [Action] is [Move Upward] or [Move Downward], set the
number of moves for one touch from 1 to 2,048.
Get Operation Log
Specifies whether to get the operation log when one of the
following actions occur: [Transfer from SRAM to Device/PLC],
[Transfer from SRAM to Internal Device], [Transfer from Device/PLC
to SRAM], [Transfer from Device/PLC to Internal Device], [Transfer
from Internal Device to SRAM], or [Transfer from Internal Device to
Device/PLC].
Data
Transfer Switch
Action
Select the switch operation for the Special Data Display [Data
Transmission]: CF/USB to Device/PLC], [Transfer from Device/PLC to
CF/USB], [Scroll Up], [Scroll Down] or [CSV Data Display].
Samples to Scroll
When [Action] is [Scroll Up] or [Scroll Down], set the number of
moves for one touch from 1 to 100.
Get Operation Log
Specifies whether to get the operation log when [Transfer from
CF/USB to Device/PLC] or [Transfer from Device/PLC to CF/USB] is
selected as the [Action].
Switch for CSV Display
Action
You can set the Special Data Display [CSV Display] switch's
action to [Scroll Up], [Scroll Down], [Scroll Left], [Scroll
Right], [Print-All], or [Print-Display].
Samples to Scroll
When selecting [Scroll Up], [Scroll Down], [Scroll Left], or
[Scroll Right], set the number of moves for one touch from 1 to
1000.
Movie Player Switch
Action
Select the switch function for playing a movie with [Movie
Player] from [Play], [Stop], [Pause], [Fast Forward], [Rewind],
[Slow Motion], [Forward 1 Frame], [Back 1 Frame], [Change Movie],
[Zoom], [Move], or [Video Display].
Speed
When selecting [Slow Motion] under [Action], specify the play
speed from [x 1/2], [x 1/4] or [x 1/8].
Step Forward Settings
When the [Action] is set to [Forward 1 Frame], select [Multiple
Frames] or [Single Frame]. This switch can be used only in the
pause state.
Detail Action
When selecting [Change Movie] as the [Action], select [Next],
[Previous], or [Specify Range].
When selecting [Next] or [Previous], specify
whether to loop the file.
Specify the Index Number from 0 to 99 of the
movie to play.
When selecting [Move] under [Action], select [Top], [Bottom],
[Left], or [Right]. The following describes the range in which a
movie can be moved at one time.
Direction
|
When playing an SDX file
|
When playing a video
|
Landscape direction
|
2 dot unit
|
2 dot unit
|
Portrait direction
|
Normal size
2 dot unit
1/4 and 1/16 sizes
1 dot unit
|
1 dot unit
|
Detail Action
When selecting [Video] as the [Action], select [Video ON],
[Video OFF], or [Video ON/OFF].
Action Mode
When selecting [Zoom] as the [Action], select [Direct] or
[Indirect].
When selecting [Direct], select the display
size from [Normal], [1/4], [1/ 16], or [Zoom].
The [Zoom] option zooms a movie in or out in this order: Normal
-> 1/4 -> 1/16 -> 1/4 -> Normal, and so on, each time
the switch is pressed. [Loop], when selected, zooms the movie in
and out in the order of "Normal -> 1/4 -> 1/16 - Normal ->
1/4...".
Designate an address to store the display
size when [Indirect] is selected.
The display sizes are as follows.
0: Standard
1: 1/4
2: 1/16
3 to 0xFFFE Reserved (no change)
0xFFFF: Normal (return to the main
screen)
Start Monitor Switch
Action
Select from [Ladder monitor], [Ladder monitor (Cache)] or
[Device monitor].
Start the ladder monitor screen. The ladder
is displayed after start and [Read]. The ladder is not displayed at
start up.
Displays the previous ladder saved on the CF
card upon exiting.
Start the Device monitor screen.
40.4
Monitoring the Value of Device Addresses (Device Monitor)
Get Operation Log
Specifies whether to record the Operation Log.
Start Application
Use the Start Application switch for starting the application by
touch when using WinGP.
EXE path
Input the absolute path of the executable file (.exe) you want
to start. You can input up to 255 characters.
Parameter
Input the argument of the executable file on start up. You can
input up to 255 characters.
Prevent multiple instances
Set [Window Title] to watch multiple instances. You can input up
to 63 characters.
If a window matching [Window Title] is found, the application
does not start. In [Window Title], if there are no settings in this
field, multiple starts are allowed.
Find whole window titles only
If a window matching the title specified in [Window Title] is
found, the specified application does not start.
Get Operation Log
Specifies whether to record the Operation Log.
Exit WinGP
Exit WinGP.
Display Confirmation Dialog Box
Display a confirmation dialog when exiting WinGP.
Get Operation Log
Specifies whether to record the Operation Log.
|