23.11 Global Interlock's Touch
Enable Condition
Enabling or disabling touch varies depending on the state of the
settings of parts used in the project or the state of the
connection with the external Device/PLC. This section explains each
setting's Touch Enable / Disable conditions.
Simultaneous use of parts with interlock
The Interlock installed on individual parts and global interlock
can be used simultaneously, but when simultaneously used, the
global interlock will take priority.
For example, even if the interlock for the individual parts is
released, touch is disabled for that part if it is in a state of
global interlock.
Specifies the address of the external
Device/PLC
When the address of the external Device/PLC is designated as the
global interlock address, Touch Enable Condition cannot be
determined until the connection with that Device/PLC is
established. Therefore, regardless of [Enable when Bit is
ON]/[Enable when Bit is OFF], the global interlock will be
enabled.
However, if disconnected once a connection is established, the
status will be the same as prior to disconnection.
-
When connecting multiple devices/PLCs, as long
as communication is established with the PLC device address used
for global interlock, global interlock will operate regardless of
the communication status with other PLCs.
-
Display settings for each part that indicates
the state of the Interlock can be applied to the interlock
condition for that part. It cannot be applied to the state of
global interlock.
Delay Feature / Group with Auto OFF switch
operations
When global interlock is enabled (touch is disabled) while a
switch delay or automatic off function is running, there are cases
where the switch operation will end and cases when the switch
operation will continue.
When global interlock is enabled (touch is
disabled) on a momentary switch set up with OFF Delay or Group with
Auto OFF, any momentary operations will continue during the delay
or automatic OFF feature.
Bit Operation: Bit Momentary
Option Settings: Enable [Reverse Display] or
[Buzzer]
When global interlock is enabled (touch is
disabled) during a ON Delay or Double Touch operation, the
operation is canceled.
Bit Operation: Bit Momentary
Option Settings: Enable [Reverse Display] or
[Buzzer]
|