23.13.4 Recording Timing of the Operation Log
Recording timing of the operation log differs depending on the
target features to be recorded.
Basic Switch Action
The previous value is not recorded.
The operation log records only state
changes.
Example, when "100" changes to "200", only the data "200" is
saved.
The operation log records only state
changes.
Example: When "100" is changed to "200", only the data of "200" is
saved.
When [Touch Panel Detection] is [ON
Detect]
Log recording is run by turning the switch
ON. For Momentary, data value recording is run when the state
toggles ON or OFF.
The operation log recording starts after the
delay time has elapsed.
The operation log recording starts when the
double touch is enabled.
When [Touch Panel Detection] is [OFF
Detect]
Log recording is performed by turning the
switch OFF. Only values after the change are saved are logged.
The operation log recording is performed when
the switch is pressed for the second time.
Data Display
The previous value is recorded at the time when Allow Data Input
is triggered, and the data for the changed value is recorded at the
time when Input is fixed.
The previous value is recorded when Input Permitted is
triggered. If a cancel is performed after that, the data of the
previous value is discarded without performing the operation log
recording.
|