Action Mode
Specify the type of operation that triggers the action.
You can select: [Bit Set], [Bit Reset], [Word Set 16], or [Word
Set 32].
Bit Set
At Start Time, the specified bit turns ON. At the End Time, the
bit turns OFF.
Example
Start Time:09:00:00
End Time:17:00:00
Bit Reset
At the Start Time, the specified bit turns OFF. At the End Time,
the bit turns ON.
Example
Start Time:09:00:00
End Time:17:00:00
Word Set 16/Word Set 32
At the Start Time, the specified [Write Start Value] is written
to the word address. At the End Time, the [Write End Value] is
written.
Example
Device Address: D0100
Start Value:10
End Value: 0
Start Time:09:00:00
End Time:17:00:00
Action Address
Designate the address used to control the schedule.
Power-ON Start/End Action
Select the action to perform when power is turned on.
If the GP unit power is turned ON outside of
the scheduled range, the termination action is performed.
If power is turned ON but the time is later
than the Start Time, the action is not automatically performed.
However, the termination action is automatically performed.
Also, if the termination action is not set, the schedule range is
not recognized and the action is not performed.
Word Write Value Settings
These settings are active only when the Mode is set to [Word Set
16] or [Word Set 32].
Constant/Address
Select the method to set the [Write Start Value] and [Write End
Value].
Write and designate a set constant.
Set the address that stores the value. You
can change the [Write Start Value] and [Write End Value] by
changing the value to store.
Sign +/-
When [Constant] is selected, specify how to handle negative
values.
Dec/BCD/Hex
When [Constant] is selected, select the data format of [Write
Start Value] and [Write End Value].
Write Start Value
Designates the value of the start time.
Designates the address used to store the
start time value.
Write End Value
Designates the value of the end time.
Designates the address used to store the end
time value.
Prohibit Action Bit
Select to prohibit the schedule function. At the beginning of
the schedule, the designated value is read out from the [Prohibit
Action Bit] address. If the [Prohibit Action Bit] is ON, the
schedule action is not performed.
Bit Address
Choose an address for the [Prohibit Action Bit].