24.4.4.1 Time Setting Address Details
Control:
Address (Time Setting Address +0)
When the Time Acquisition Request bit's ON (0 to 1) is detected,
the Mode, Start Time, and End Time are read out.
Bit 00: Time Acquisition Request Bit (0: No action, 1: Perform
Time Read)
Status (Time
Setting Address+1)
After the Control time data readout is completed, the display
unit will turn the Time Acquisition Completion Bit ON (0 to 1).
Also, if the entered time data is incorrect, the Error Notification
Bit will simultaneously turn ON (0 to 1).
Bit 00: Time Acquisition Completion Bit (0: Either Time
Acquisition is being performed or had not yet been performed, 1:
Time Data Acquisition Completed)
Bit 01: Error Notification Bit (0: Time data is being replaced
with correct data. 1:Time data contains an error.)
-
Once the Time Acquisition Completion bit's rise
(trigger) is recognized by the Device/PLC, be sure to turn the
control Time Acquisition Request bit OFF (1 to 0).
Once this bit is turned OFF (1 to 0), the Status Time Acquisition
Completion bit and the Error Notification are simultaneously turned
OFF (1 to 0).
-
When the [Power-on Start/End Action] is set up,
even if the Request Time bit is not ON, gets the time and only the
status turns ON. In that condition, if you want to clear the
status, you can directly update the status address value.
Mode (Time
Setting Address+2)
Enable and disable the Termination Time Action and the
Individual Day settings. Regardless of the Termination Time Action
status, the indirectly designated time data (11 word addresses in
the Time Setting Address) are read out.
Bit 00:Termination Time Action Setting (0: None, 1: Used)
Bit 01: Individual Day Specification Mode (0: None, 1: Used)
-
If a [0] (Not Used) is entered in the
Individual Day Specification mode, the End Time data are read but
ignored.
-
If a [1] (Used) is entered in the Individual
Day Specification mode, be sure to enter all Start and End time
information. If 2 or more of the Start/End Day bits turn ON
simultaneously, an error occurs.
Start/End
Day (Start Day: Time Setting Address +3, End Day: Time Setting
Address +7)
Designates the day used as a trigger for the Start/Termination
Action.
Bit 00: Sunday (0: None, 1: Used)
Bit 01: Monday (0: None, 1: Used)
Bit 02: Tuesday (0: None, 1: Used)
Bit 03: Wednesday (0: None, 1: Used)
Bit 04: Thursday (0: None, 1: Used)
Bit 05: Friday (0: None, 1: Used)
Bit 06: Saturday (0: None, 1: Used)
Start/End
Time: (Start Time: Time Setting Address +4 to +6, End Time: Time
Setting Address +8 to +10)
(Start Time: Time Setting Address +4 to +6, End Time: Time
Setting Address +8 to +10) Set the time values used for the
Start/Termination Actions in the following ranges.
Hours: 0 to 23
Minutes: 0-59
Seconds: 0-59
-
Time data are specified with Bin format. They
cannot be specified with BCD format.
-
The End Time depend on the Mode (address +2)
setting.
Also, the Termination Time Action setting (bit 00) available
depends on the Individual Day Specification mode (bit 01) used.
Individual Day Specification
|
Used
|
Not
Used
|
Termination Time Action Setting
|
Used
|
Used
|
Not Used
|
|