You can print up to 160 characters per line.
Characters that exceed the maximum are not printed.
-
You cannot designate the size of the characters
to print.
-
The number of characters that can be printed on
one line depends on the printer and paper size. When the characters
in a single line do not fit onto the paper width, the outputted
results will differ depending on the font and printer.
-
Standard Font
When text does not fit the paper width, there are printers that do
not print text outside the paper width, printers that automatically
insert line breaks to print all text from each line, and printers
that do not print properly.
-
Stroke Font
Text that does not fit the paper width does not print.
-
Regardless of the printer color settings
(monochrome/color), all data is printed in black and white.
-
When the sampling group font type is set to
[Stroke Font] and the language is set to [Standard Font] of [Chinese (Traditional)],
[Chinese (Simplified)],
or [Korean], text will
be printed out as image data, and it may take some time to
print.
-
If real-time printing of another sampling group
occurs during a real-time print, data will be mixed. It does not
separate each sampling group.
-
DO NOT enter other printing commands during
real-time printing. If an Alarm History printing command occurs
during real-time printing, the alarm history and other data will be
mixed together during printing.
-
Some printers used cannot print per line in
real-time printing. This is because the printers don't support
paper feed per line.
-
If sampling data is deleted during printing,
printing will not continue. If the display unit is turned OFF
during printing, jobs in the queue are lost.
-
The calculation operations are carried out in 32
bit length. If the calculation data has more digits (exceeds 32
bits), the correct value will not be printed.
-
If sampling data changes when the [Overwrite old
data after finishing the specified cycles] check box is selected,
the printing speed can be slower than the data overwrite and store
speed if the [Occurrences] is small or a short Sampling Cycle is
being used. When sampling data is overwritten before printing, the
data prior to the overwrite cannot be printed.
-
In the sampling group's Address, if the [Bit
Length] or [Addressing] change, the print format will be reset.
-
When changing the print mode from [Custom
Settings] to [Basic], all customized settings will be reset.
-
When using Custom Settings, the maximum number of
columns that can be set with the print format is 521 columns. The
maximum number of rows is 4204.
The maximum number of columns is the total of the Date, Time, Data,
Text, and Ruled Line columns. Header/footer areas are not
included.
-
Please use the same data format for the numeric
value and total fields. If the formats differ, then the calculated
value may not display correctly.
-
If sampled data exists from the time batch print
is started (the Print Control Address bit is turned ON) to the time
[Print Completion Bit Address] is turned ON, the data will be
printed. However, a print time lag occurs from the time when a
display unit determines that all sampled data is printed (no more
updated sampled data) and turns on the print completion bit ON. Any
sampled data during that time will not be printed.