25.11.4 Saving to CSV
There are two save operations for CF Cards/USB storage
devices.
When the command is written to the [CSV
Control Word Address], data stored in the display unit is output as
a CSV file.
25.6.2 Operation - Normal Save
When the defined number of samples are stored
in the display unit and the sampling cycle is complete, data stored
in the display unit is output as a CSV file. This option is
available when in the [Mode] tab, [Extended] dialog box, you select
the [Overwrite old data after finishing the specified cycles] check
box.
25.6.3 Operation - Automatic
Save
CSV Control Word Address
This address controls the writing of data to a CF Card/USB
storage device. It writes a command to the address after
designating a file number.
After you specify the file number and write
the command to the control address, data is output to the CF card
or USB storage device. The processing results (status) are
reflected in the address.
Mode
|
Word Data
|
Description
|
Command
|
0001h
|
Normal Save
|
0020h
|
Start Auto Save (Only when data is stored by
overwriting old data*1)
|
0021h
|
End Auto Save (Only when data is stored by
overwriting old data*1)
|
Status
|
0000h
|
Completed Successfully
|
0100h
|
Write Error
|
0200h
|
The CF Card is not inserted/CF Card cover is
open (access switch is OFF)/USB storage device is not inserted
|
0300h
|
No data to be loaded
|
0400h
|
File Error
|
2000h
|
The display unit is in the normal Auto Save
mode.
While the [CSV Save Control Address] has this value, the Auto Save
action continues. When the value changes, the Auto Save mode
finishes.
|
-
When you change the value of status "2000h" or
change the file number during the Auto Save process, Auto Save is
exited and data up to then is written to the CF Card/USB storage
device. The write command is not processed. The status will show
successful completion "0000h".
-
When a value other than "0001h", "0020h", or
"0021h"is written in a command or the value "0021h" is written
instead of "0020h", it will cause a write error "0100h".
-
When the Auto Save command "0020h" is written
in the sampling group without the selection of the [Overwrite old
data after finishing the specified cycles] check box, "0300h" error
occurs.
Designates the ***** portion in the file name, "SA*****.csv", when
saving to the CF Card/USB storage. The file number can be from 0 to
65535. Set the file number before writing the command.
The CSV File is saved to the folder created
in the CF Card/USB storage device automatically. The folder is
created with a fixed folder name for each sampling group.
Data to be saved
|
Folder
|
File Name
|
Sampling Group 1 data
|
\SAMP01
|
SA*****.CSV
|
.
.
.
|
.
.
.
|
|
Sampling Group 64 data
|
\SAMP64
|
SA*****.CSV
|
|