26.10.3.2 Control Word
Address when Using the Condition Name Search Feature
After storing the Condition Name to search, turn the [Control
Word Address] transfer bit (bit 2) from OFF to ON to : search for
CSV files within the CF Card/USB storage and transfer all CSV files
that match the search condition name.
When bit 2 turns ON, search for the file with
the condition name that matches the text string designated in
[Search Word Address], and write the matching CSV data to the
PLC.
-
Ensure that all bits in this address are set to
"0" when the GP unit is turned on.
-
When bit 0 (CF/USB to Device/PLC) and bit 2
(Condition Name Search transfer) turn ON at the same time, neither
operation is performed. Turn ON only bit 2.
Transfer state and result is reflected in
this address.
Error Codes (Reflected in the error status
bits)
0
|
Completed Successfully
|
Transfer completed successfully.
|
1
|
No File Number
|
When transferring from CF Card/USB Storage to
the device/PLC, there were no files to transfer.
|
2
|
No Transfer Condition Number
|
For transfer, the Condition Number that
corresponds to the specified File Number (GROUP NO) does not
exist.
|
3
|
Internal Device Range Error
|
When transferring from CF Card/USB Storage to
the device/PLC and the start address is set up as an internal
device, transfer would exceed the internal device address
range.
|
4
|
No CF Card or USB Storage
|
The CF Card/USB storage is not inserted in the
display unit, or the CF Card cover is not closed.
|
5
|
Read Error
|
When transferring from the CF card/USB storage
to the device/PLC, failed to read data on the CF card or USB
storage device.
|
6
|
Write Error
|
When transferring from the device/PLC to CF
card/USB Storage, failed to write to the CF Card or USB Storage.
There may not be enough available space.
|
7
|
CF Card Error/USB Storage Error
|
The CF Card/USB storage device is invalid or
the media inserted is not a CF Card/USB storage device.
|
8
|
Reserved
|
—
|
9
|
No Retrieve Text
|
No CSV file matches the retrieve text.
|
10
|
Index File Error
|
The index file's CSV format is incorrect.
|
11
|
Reserved
|
—
|
12
|
Write Error
|
When transferring data from CF Card/USB storage
to the device/PLC, failed to write to the device/PLC.
|
13
|
Read Error
|
When transferring data from the device/PLC to
CF Card/USB storage, failed to read the device/PLC.
|
Condition Name Search Transfer Timing
Chart
When the control address' bit 2 turns ON, the [Transferring] bit
(status bit 0) turns ON.
When a data transfer is completed successfully, the Transferring
bit turns OFF, and the Transfer Complete Flag (status bit 1) turns
ON.
When the data transfer is completed, determine the Transfer
Complete Flag via the device/PLC and turn OFF the Control Address'
bit. When the trigger is OFF, the [Transfer Completion] bit turns
OFF.
If the transfer fails, the Transferring Bit turns OFF, and the
error code is set in the error status (status bits 12-15). Before
starting the next transfer, clear the Status and Control bits to 0
and turn on the required Control bit.
|