Displays each slave diagnosis status list.
Assigned
Slaves
Displays the used (Assigned) slaves in the GP-Pro EX
Project.
CANopen Master
Configuration
Displays which slaves in the network are configured by CANopen
Master.
Faulty
Slaves
Displays slaves that did not send heartbeat in time, were not
yet initialized and had a faulty cDCF file.
Emergency
Slaves
Displays slaves that have sent an emergency message. The details
of the emergency message can be read from the object 0x2018. You
can read the Node ID as Sub-Index.
Operational
Slaves
Displays slaves which are in Operational State.
Stopped
Slaves
Displays currently stopped slaves.
Preoperational
Slaves
Displays slaves which are in pre-operational mode.
Mismatch
There is a format error in the project.
cDCF
Mismatch
There is an error in the project settings.
Inconsistent
cDCF
There is an error in the project settings. Identity error can be
one of the following:
-
Device ID Error [OBJECT - 0x1F84]
-
Device type [OBJECT - 0x1000]
-
Identity Object [OBJECT - 0x1018]
-
Vendor ID Error [OBJECT - 0x1F85]
-
Product Code Error [OBJECT - 0x1F86]
-
Revision # Error [OBJECT - 0x1F87]
Displays an I/O driver error message. For details on the errors
to be displayed, refer to the following: