M.9.3 Checking Communication
with the FLEX NETWORK
Check if the input and output operate
normally
Can the device connected to the FLEX NETWORK board perform input
and output functions normally?
Check if GP-Pro EX settings are the problem, or the display unit is
the problem.
When DIO
(Example: FN-X16TS) is used
-
Go to offline mode and touch [Peripheral Settings] on the item
changeover switch.
-
[Peripheral
Settings] screen opens. Touch [I/O Driver] and then [FLEX NETWORK Driver].
-
[I/O
Driver] screen opens. Touch [I/O Monitor].
-
[I/O
Monitor] screen opens. Set the [Transmission Speed], [S-No.], [Model], and [Type]. (Example, S-No.= 1, Model= Input FN-X16TS, Transmission Speed= 6Mbps,
Type=Bit)
-
The bit monitor screen is displayed, showing the
ON/OFF status. A protruding switch indicates OFF and a depressed
switch indicates ON. If the connected device is operating normally,
check the settings in GP-Pro EX. If the connected device does not
operate normally, check the wiring between the display unit and the
connected device, and then check the following items.
When an analog unit (Example: FN-AD02AH) is
used
-
Go to offline mode and touch [Peripheral Settings] on the item
changeover switch.
-
[Peripheral
Settings] screen opens. Touch [I/O Driver] and then [FLEX NETWORK Driver].
-
[I/O
Driver] screen opens. Touch [I/O Monitor].
-
[I/O
Monitor] screen opens. Set the [Transmission Speed], [S-No.], [Model], and [Type]. (Example, S-No.= 1, Model= Input FN-AD02AH,
Transmission Speed=
6Mbps
-
Touch this switch to go to the next screen and set
[CH] (channel) and
[Range].
-
The input monitor screen is displayed. The input
status is indicated with an integer value. If the connected device
is operating normally, check the settings in GP-Pro EX. If the
connected device does not operate normally, check the wiring
between the display unit and the connected device, and then check
the following items.
Checking
communication to ensure proper cable connection
Check whether the FLEX NETWORK unit connected to the FLEX
NETWORK board can communicate properly.
-
Go to offline mode and touch [Peripheral Settings] on the item
changeover switch.
-
[Peripheral
Settings] screen opens. Touch [I/O Driver] and then [FLEX NETWORK Driver].
-
[I/O
Driver] screen opens. Touch [Check Comm.].
-
[Start]: Touch the button.
-
The communication check screen will display. When
no problem is found with the communication, the total number of
units that communicated successfully and the S-No assigned to the
units are highlighted. If communication is successful, please check
whether the device connected to the FLEX NETWORK unit operates
properly or the cable is correct. If communication fails, check the
communication cable for breaks, the power supply of the unit, and
the termination resistor of the unit. If the problem continues, the
I/O unit or display unit may be faulty. Please contact the Pro-face
customer care center.
The following list shows the I/O units supported by the
communication check. For example, when setting FN-X16TS(1),1 S-No.1
and FN-XY32SKS (4),1,S-No.2, S-no.1 to 5 are highlighted on the
screen above.
Type
|
Model
|
Number of stations
|
DIO
|
FN-X16TS
|
1
|
FN-X32TS
|
2
|
FN-Y08RL
|
1
|
FN-Y16SK
|
1
|
FN-Y16SC
|
1
|
FN-XY08TS
|
1
|
FN-XY16SK
|
1
|
FN-XY16SC
|
1
|
FN-XY32SKS
|
4
|
Analog
|
FN-AD02AH
|
1
|
FN-AD04AH
|
4
|
FN-DA02AH
|
1
|
FN-DA04AH
|
4
|
High Speed Counter Unit
|
FN-HC10SK
|
8
|
Single-Axis Positioning Unit
|
FN-PC10SK
|
4
|
|