M.9.5 Checking if communication with
the EX modules is enabled
Check if the EX modules are connected correctly to the LT series
and check if the input and output of the device connected to the EX
modules are operating properly, to judge whether the problem is
caused by GP-Pro EX settings or by the LT series.
When the DIO module is used
I/O check is available only with EX modules set
up in GP-Pro EX.
Go to offline mode and touch [Peripheral Settings] on the item
changeover switch.
[Peripheral
Settings] screen opens. Touch [I/O Driver] and then [EXM Driver].
[EXM
Driver] window opens. Touch [I/O Mntr] to display the number of
currently connected modules and the module numbers. If the
connected module is not displayed, check the wiring between the
module and the connected device.
When the LT3200 series is used, up to 2 modules
are displayed. When the LT3300 series is used, up to 3 modules are
displayed.
Touch each module number. After the corresponding
screen appears, select the type of input/output data, [Bit] or [Word]. (Example, DIO=Output 16
points, Type=Bit)
If you shift between screens with the switch, the input/output
execution screen appears, which displays the input ON/OFF status
and allows you to execute the output. If the connected device is
operating normally, check the settings in GP-Pro EX. If the
connected device is not operating normally, check the wiring
between the EX module and the connected device.
When the analog module is used
I/O check is available only with EX modules set
up in GP-Pro EX.
Go to offline mode and touch [Peripheral Settings] on the item
changeover switch.
[Peripheral
Settings] screen opens. Touch [I/O Driver] and then [EXM Driver].
[EXM
Driver] window opens. Touch [I/O Mntr] to display the number of
currently connected modules and the module numbers. If the
connected module is not displayed, check the wiring between the
module and the connected device.
When the LT3200 series is used, up to 2 modules
are displayed. When the LT3300 series is used, up to 3 modules are
displayed.
Touch each module number. After the corresponding
screen appears, specify the I/O channel number, data format, and
data range. (Example, CH=1, Data Format=Voltage (0-10 V),
Data Range=Fixed)
If you shift between screens with the switch, the input/output
execution screen appears, which displays the input value and allows
you to execute the output. If the connected device is operating
normally, check the settings in GP-Pro EX. If the connected device
is not operating normally, check the wiring between the EX module
and the connected device.