Configures settings for module temperature input terminals.
Data Format
Select the thermocouple input data format from [Disable], [K
Thermocouple], [J Thermocouple], [T Thermocouple], or [Pt100].
K Thermocouple (Celsius/Fahrenheit)
The K thermocouple temperature range is as follows.
The displayed value is 10 times (0 to 13000)
the input value ranging from 0.0°C to 1300.0°C.
The displayed value (320 to 23720) is 10
times the input value (32.0°F to 2372.0°F).
J Thermocouple (Celsius/Fahrenheit)
The J thermocouple temperature range is as follows.
The displayed value is 10 times (0 to 12000)
the input value ranging from 0.0°C to 1200.0°C.
The displayed value (320 to 21920) is 10
times the input value (32.0°F to 2192.0°F).
T Thermocouple (Celsius/Fahrenheit)
The T thermocouple temperature range is as follows.
The displayed value is 10 times (0 to 4000)
the input value ranging from 0.0°C to 400.0°C.
The displayed value (320 to 7520) is 10 times
the input value (32.0°F to 752.0°F).
Pt100 Celsius/Fahrenheit
The temperature range of PT100 is shown below.
The displayed value is 10 times (-1000 to
5000) the input value ranging from -100.0°C to 500.0°C.
The displayed value (-1480 to 9320) is 10
times the input value (-148.0°F to 932.0°F).
Configures settings for module analog output terminals.
Data Format
Select a data type from either [Voltage (0-10V)] or [Current
(4-20mA)] for analog output.
Fixed
The analog values in the voltage and current
output settings appear in the range of 0 to 4095 as shown
below.
User Defined (Maximum/Minimum)
The analog values in the voltage and current output settings
appear within the range of [Maximum] and [Minimum] settings.
The available values are as follows.
Maximum: minimum to 32767
Minimum: -32768 to maximum
Retentive Output
Select whether or not you want to retain output values when the
logic is stopped. Select [Enable] to retain output values even if
the logic stops.