Input Area
Area you can use for inputs is divided into 28 x 16-bit
areas.
The Input Area field displays the input area number and
associated bits in brackets "input area number (start bit - end
bit)". You cannot edit the Input Area.
Input Type
Select the input type from either [Bit] or [Word].
Output Area
Area you can use for outputs is divided into 28 x 16-bit
areas.
The Output Area field displays the output area number and
associated bits in brackets "output area number (start bit - end
bit)". You cannot edit the Output Area.
Output Type
Select the output type from either [Bit] or [Word].
Retentive output when controller ends
Select whether or not you want to retain output values when the
logic program stops. Select the check box to retain outputs.
-
The following operations will reset
outputs.
-
Turn OFF the display unit.
-
Restart the display unit.
-
Go to offline mode.
-
Run project transfer with [Transfer Project]
set to [Automatic] or [Retain retentive variables].
Required scan time
Displays the scan time with the current settings and I/O points
as : XX milliseconds (Input/Output: YY Points/ZZ Points).
Area in Use*1
|
I/O Points
|
Required scan time
|
Unused or 0 to 1
|
Input/Output: 32Points/32Points
|
10 ms
|
2 to 3
|
Input/Output: 64Points/64Points
|
10 ms
|
4 to 7
|
Input/Output: 128Points/128Points
|
10 ms
|
8 to 11
|
Input/Output: 192Points/192Points
|
14 ms
|
12 to 15
|
Input/Output: 256Points/256Points
|
18 ms
|
16 to 19
|
Input/Output: 320Points/320Points
|
22 ms
|
20 to 23
|
Input/Output: 384Points/384Points
|
26 ms
|
24 to 27
|
Input/Output: 448Points/448Points
|
30 ms
|
-
When the send/receive values between the first
and second cycles match, the I/O status is updated. When the data
values had changed in the second cycle, the I/O status is not
updated.
The approximate communication time for one cycle is as follows.
I/O Points
|
Approximate communication time
|
Input/Output: 32Points/32Points
|
1.7 ms
|
Input/Output: 64Points/64Points
|
2.7 ms
|
Input/Output: 128Points/128Points
|
4.8 ms
|
Input/Output: 192Points/192Points
|
6.8 ms
|
Input/Output: 256Points/256Points
|
8.9 ms
|
Input/Output: 320Points/320Points
|
10.9 ms
|
Input/Output: 384Points/384Points
|
13.0 ms
|
Input/Output: 448Points/448Points
|
15.0 ms
|
-
From the [System Settings], in the [Logic
Programs] page, when [Register Variable] uses the [Address Format]
option, the required scan time is 30 milliseconds as all I/O are
mapped.