31.7.6.11 Analog Output (Model:
EXM-AMO1HT)
The analog output module defines output range, customizable
value, and fallback value using configuration object.
|
Channel
|
Object (Hex)
|
Sub index
|
Description
|
Parameter
|
|
CH1
|
2200
|
n
|
Data Format
|
0: Disable
2: Current (4 to 20mA)
3: Voltage (0 to 10V)
|
|
2201
|
n
|
Data range
|
0: Fixed
1: User setting
|
|
2202
|
n
|
Lower limit
(when 2101h = 1)
|
Lowest value
|
|
2203
|
n
|
Upper limit
(when 2101h = 1)
|
Highest value
|
|
6411
|
n
|
Written value
|
Output
|
|
6443
|
n
|
Fallback mode
|
0: Retentive State
1: Fallback
|
|
6444
|
n
|
Fallback Value
(when 6443h = 1)
|
Fallback Value
|
|