Error Code
|
Error Message
|
Description
|
Solution
|
001
|
Not supported unit.
|
This model is incorrect. (Model of supported
unit.)
|
The project file might not have been sent
properly. Transfer the project file again.
|
002
|
Setting value error
|
The data type of the symbol variable assigned
to the FLEX NETWORK unit is illegal. The FLEX NETWORK unit setting
value is illegal.
|
003
|
Device
out-of-range error
|
The address of the symbol variable assigned to
the FLEX NETWORK unit is out of range.
|
004
|
Duplicate
terminal settings
|
The number of FLEX NETWORK unit terminals
exceeds the limit.
|
005
|
Terminal setting
order error
|
The I/O terminal numbers are not set up in
ascending order.
|
006
|
Terminal
registry short
|
Not a reasonable number of I/O terminals.
|
007
|
Units config
overlapped.
|
FLEX NETWORK unit station number is duplicated
and set.
|
008
|
Units count over
limit.
|
The maximum number of connected FLEX NETWORK
units (63 units) is exceeded. The maximum value of station number
(S-No.63) is exceeded. The S-No of the FLEX NETWORK unit that
occupies more than one node has exceeded the maximum (S-No 63).
|
009
|
Repeat driver
setting
|
The driver is registered twice.
|
010
|
Unmatched In/Out
terminal.
|
The input/output settings of the FLEX NETWORK
unit are not correct.
|
011
|
Unmatched
bit/word term.
|
The variable type specified in the FLEX NETWORK
unit is incorrect.
|
012
|
Setting level
value error
|
There is a problem with the I/O driver.
|
013
|
Data obtaining
address error
|
I/O driver information is incorrect. Invalid
controller information.
|
014
|
Driver/unit not
registered
|
The I/O driver or FLEX NETWORK unit is not
registered.
|
Error Code
|
Error Message
|
Description
|
Solution
|
100
|
Unit
communication error.
|
A communication error has occurred between the
main unit and the FLEX NETWORK unit. Possible causes are that the
communication cable is disconnected; the FLEX NETWORK unit is not
connected; or an incorrect unit model is set in the project
file.
|
The station number or communication speed set
in the editor may differ from that set in the unit. If this error
continues, check the following.
|
101
|
4ch analog
setting error.
|
Communication with the 4 CH analog unit has
failed.
|
Please check the following.
-
Comunication cable connection
-
Unit's power supply
-
Unit's termination resistor settings
-
Editor settings and model of the connected
unit
|
102
|
2ch analog
setting error.
|
Communication with the 2 CH analog unit has
failed.
|
103
|
Analog unit’s
wire broken.
|
The 4 to 20mA-ranging input signal of the 4 CH
or 2 CH analog unit is cut off. This error code continues to
display unitl the controller is reset.
|
Check if the input signal is disconnected.
|
104
|
Counter unit
error.
|
An error has occurred in the high-speed counter
unit.
|
For details, find the associated unit’s error
code in the following manual.
FLEX NETWORK High Speed Counter
Unit User Manual
|
105
|
Counter initial
error.
|
Initializing the high-speed counter unit has
failed.
|
Please check the following.
-
Comunication cable connection
-
Unit's power supply
-
Unit's termination resistor settings
-
Editor settings and model of the connected
unit
|
106
|
Counter communication error.
|
A communication error with the high-speed
counter unit has occurred.
Possible causes of this error are that the communication cable is
disconnected; the high-speed counter unit is not connected; or an
incorrect unit model is set in the project file.
|
107
|
Positioning Unit
error.
|
An error has occurred in the positioning
unit.
|
For details, find the associated unit’s error
code in the following manual.
FLEX NETWORK Single-Axis
Positioning Unit User Manual
|
108
|
Comm position
error.
|
A communication error with the positioning unit
has occurred.
Possible causes of this error are that the communication cable is
disconnected; the positioning unit is not connected; or an
incorrect unit model is set in the project file.
|
Please check the following.
-
Comunication cable connection
-
Unit's power supply
-
Unit's termination resistor settings
-
Editor settings and model of the connected
unit
|
109
|
2ch analog comm error.
|
A communication error with the 2 CH analog unit
has occurred.
Possible causes of this error are that the communication cable is
disconnected; the 2ch. analog unit is not connected; or an
incorrect unit model is set in the project file.
|