Error Code
|
Error Message
|
Description
|
Solution
|
002
|
Illegal
parameter
|
The data type of the symbol variable assigned
to the I/O is incorrect.
There is a problem with the I/O setting value.
|
The project file might not have been sent
properly. Transfer the project file again.
|
003
|
Device offset
beyond limit.
|
The address of the symbol variable assigned to
the I/O is out of range.
|
004
|
Terminal config
overlapped.
|
The number of I/O terminals exceeds the limit
(6 bit inputs and 2 bit outputs).
|
005
|
Illegal terminal
sequence.
|
The I/O terminal numbers are not set up in
ascending order.
|
006
|
Insufficient
terminals.
|
The number of I/O terminals is not appropriate
(insufficient).
|
009
|
Driver config
overlapped.
|
The driver has been registered twice.
|
011
|
Unmatched
bit/word term.
|
The variable type specified in the I/O is
incorrect.
|
012
|
Illegal level
number
|
Something is wrong with the I/O driver.
|
013
|
Illegal data
address gotten.
|
The I/O driver information is incorrect. The
controller information is incorrect.
|
014
|
Driver/Units not
registered.
|
The I/O driver or I/O is not registered.
|
050
|
Different ID
unit connected.
|
The I/O board being connected is different from
the I/O board in the project.
|
100
|
DIO read data
chattering
|
Chattering occurred during the input from the
DIO board.
|
This may be caused by noise or display unit
failure. If this error occurs frequently, the unit may be faulty.
If the problem continues, please contact our customer care
center.
This error code continues appearing until the controller is
reset.
|
101
|
DIO write data
error
|
Although data was output to the DIO board, it
was not output when the output result was fed back.
|