This object is used to store parameters of HTB and EX module in
backup memory.
When storing parameters with this object, in
the HTB slave settings set [Restore] to either [Restore All] or
[Communication only]. Communication may not work properly when
selecting any other option.
Properties of the object
Object properties:
Sub index
Description
Data Type
Default
Access
PDO mapping
Backup
0
Sub index number
UNSIGNED8
4
ro (read only)
×
×
1
Store all the parameters
UNSIGNED32
—
rw (read-write)
×
×
2
Store communication parameters (1000h to
1FFFh)
UNSIGNED32
—
rw (read-write)
×
×
3
Disable
—
—
4
Store application parameters (2000h to
9FFFh)
UNSIGNED32
—
rw (read-write)
×
×
Action
To store parameters, it is necessary to write "save" text (6576 6173h) to the
corresponding index.
Top byte
Bottom byte
ISO 8859 (ASCII) signature
e
v
a
s
Hexadecimal value
65h
76h
61h
73h
Information on storage feature is read from sub index. Obtained
result 0000 0001h indicates parameters are restored by the module