Displays a Base screen or Image screen based on the value stored
in a word address, [Bit Detail Settings], and [Range Settings].
Word Address
Specifies a word address for screen display
changes. The display screen number is calculated by adding the word
address value with the screen number defined in the [Select
Display] field.
Based on the timing of changes to the bit
address in the word address defined here, screen changes occur in
sequential order from the start screen defined in the [Select
Display] field.
In response to the range of data changes,
screen changes occur in sequential order from the start screen
defined in the [Select Display] field.
Bit Detail Settings
Set which bit in the word address to assign for display. The
display data is determined by the [Bit Offset] and [Bit Length]
settings.
Bit Offset
Set which bit in the Word Address to start to assign for
display. Set the offset value from 0 to 15. Set "0" when you use
all the word addresses or when offset settings are not needed.
Bit Length
Set the number of bits in the word address to assign for
display. Set up the [Bit Length] from 1 to 16. When bit offset is
not zero, you can set up the range as [Bit Offset] + [Bit Length]
<= 16. The number of change screens is determined by the [Bit
Length] settings.
Range Settings
Set the number of pictures to change and the data values at
which to change to each screen. The range of data for use depends
on the [Bit Detail] settings.
For example, when the bit offset is "3" and the bit length is
"4", the following 4 bits are used as data for change display.
Ranges
Set the number of screens to change as the number of ranges. The
setting range is from 1 to 32. However, values exceeding the [Bit
Length] cannot be displayed.
For example, when the bit length is "4", the number of ranges is
1 to 16.
Data Type
Select the data type from [Dec], [Hex], or [BCD], and select the
Range Settings [Min.] and [Max.].
Range Number
Select the [Range Number] to set.
Min
Set the minimum value of the selected range.
Max
Set the maximum value of the selected range.
The Base screen or Image screen to display is variable. Change
and display screens by storing the screen numbers in the Word
Address.
Word Address
Set the word address where the screen number to display is
stored.
Data Type
Choose the data type of the display screen address from [Bin] or
[BCD].
Offset
Set the offset value from 0 to 8999. A Base/Image screen
displays. It is defined by the value in the [Display Screen
Specification Address], plus the offset.