Enable Popup Keypad
Select whether a pop-up keypad will display when you touch the
Data Display part.
Keypad Type
Use the standard keypad registration for
GP-Pro EX. Use this in normal cases.
Create a user-defined keypad with the Keypad
part. This keypad allows for customized input.
15.6.1.2 User Keypad
System Keypad
Display the prepared standard keypad registration in GP-Pro
EX.
User Keypad
Specify Location
Select whether to set the pop-up keypad display position. If
[Enable] is selected, the pop-up keypad Display Area can be
selected and moved after the Data Display part is positioned.
Designated Input Order
When entering data into multiple Data Displays in sequence,
select the order in which each display enters the input state.
Input Order
Select the order, from 1 to 384, in which the Part will enter
the input state.
Group
Divide the Data Displays into groups for continuous data input.
The cursor will move in turn to each successive Data Display
registered in the same group, according to the input order, setting
them into the Allow Input state. The Group Number can be from 1 to
10. Continued
14.13.2 Set Input Order
by Group
Interlock
Designate whether or not to use the Address and Security Level
when using the Interlock Feature (a feature that enables Touch only
when the conditions are satisfied).
Use an Address
This function only allows input when the [Address] bit is
selected via the [Touch Enable Condition]. Select the check box to
use Interlock.
14.7 Using Interlock to Prevent
Malfunctions
Address
Select the bit address that will designate the enable condition,
to allow input to be entered. Touch is enabled (disabled) depending
on the state of this address.
Touch Enable Condition
Select the condition that will enable the part to be touched, to
allow input to be entered.
Touch Enable Condition
|
Address Status
|
Touch Enabled/Disabled
|
When Bit is ON
|
ON
|
Touch enabled
|
OFF
|
Touch disabled
|
When Bit is OFF
|
ON
|
Touch disabled
|
OFF
|
Touch enabled
|
Use Security Level
Select whether to use the security function for each part. When
logged in with a Security Level higher than that set for the part,
Touch Operation will be enabled.
Level
Set the Security Level of the part from 1 to 15.
Bit
Allow Input Bit Address
When the bit address set here turns ON, the Data Display enters
the input state.
Input Order
Number the Parts from 1 to 384 in the order that they will enter
the Allow Input state if the [Allow Input Bit Addresses] of
multiple Data Display Parts turn ON at the same time (when a bit
address has been registered to multiple Data Display parts, or when
different bit addresses turn ON at the same time).
-
If more than one [Allow Input Bit Address] is
turned ON at the same time, the Data Displays will enter the input
state according to their [Input Order] settings. If the [Input
Order] settings are the same, the input state order will be
determined by the order the parts were placed.
-
If the [Allow Input Bit Address] of Data
Displays placed on the Base Screen and Window Screen turn ON at the
same time, the Base Screen will have a higher priority for the
input state than the Window Screen. When placing Data Displays on
both the Base and Window screen, make sure to set a different
[Allow Input Bit Address].
New data will build on previously input data.
Pressing [CLR] on the keypad clears the value.
The first key pressed (except cursor moves,
[ENT], [DEL], or [BS]) will clear the previously input text
data.
When using barcode input, performs automatic
clear and checks whether the number of input digits coincides with
the [Total Display Digits]. If they do not coincide, the data will
not be written to the word address.
A setting that allows input from a barcode reader.
Detects and notifies you when input has been completed.
Sets the bit address that will turn ON when input has been
completed.