For details about placing parts or setting
addresses, shapes, or colors, please refer to the "Part Editing
Procedure". 8.7.1 Editing Parts
From the [Parts (P)] menu, point to [Data Display
(D)] and select [Numeric Display (N)], or click the icon, and place it on
the screen.
Double-click the placed Data Display. The following
dialog box appears.
Select the Data Display shape from [Select
Shape].
In [Monitor Word Address], set up the address to store the displayed numeric
value.
In the [Data Type] drop-down list, select the type
of data to display (for example, "16 Bit Dec").
Select the [Allow Input] check box. Ensure the
[Enable Popup Keypad] check box is selected. You can enter
numerical data from the pop-up keypad.
On the [Data Entry] tab, click [Extended]. The
following dialog box appears.
From the [Interlock Feature] area, select the
[Enable Address] check box and in the [Address] field specify the
bit address (M100) that will enable touch inputs.
Use the [Touch Enable Condition] options to set up
a condition that enables touch inputs. (For example, select "Enable
When Bit is Off" to enable touch operations when the bit is
off.)
As needed, set the Data Display color and text on
the [Alarm/Color] tab and [Display] tab, and click [OK].