When communicating inside the display unit using the Direct
Access Method, the LS area is secured.
This area is useful for temporarily storing control handling
within a display unit that does not have a device/PLC address (for
example, a switch's Interlock Settings), or for temporarily storing
values calculated within the display unit.
LS Area List
Do not set addresses for Parts which span
the System Data Area and Read Area, or the Read Area and User
Area.
When setting addresses for Parts in the
System Data Area, set the data length as 16 bit.
*1 The System Data Area can exclusively use a
maximum of 20 words. The Read Area can exclusively use a maximum of
256 words. The User Area's top address is the Read Area's top
address (20) + Read Area's size.