This section explains the setting procedure, using a Bit
Monitoring example.
When the Monitoring Bit Address turns ON, the Alarms are
displayed together with their trigger date/time. When the
Monitoring Bit Address turns OFF, the recovery time is added to the
same row.
-
From the [Common Settings (R)] menu, select [Alarm
(A)], or click . The following screen
appears. In [Language], select the alarm message display
language.
-
In the Block Settings, select the check box for the
desired display mode (History/Log/Active) for the block to which
the message is registered, and set the number of messages stored as
history for each mode.
-
Select [Backup History] and define [Hide Continuing
Alarms].
-
From the [Block1] tab, select [Bit Monitoring].
-
In [Bit Address], set the bit address to monitor the alarm
trigger.
-
In the [Trigger Condition] cell, select whether the
alarm is triggered when the Monitoring Bit Address turns ON or
turns OFF.
-
In the [Message] cell, input the alarm message that
will display when the alarm is triggered.
-
Up to 160 single-byte characters can be
registered in a single Alarm Message.
-
When the [Enable Text Table] check box is
selected, the message language can be switched and displayed even
while the system is running.
18.3 Changing Text to
Other Languages
-
Select the [Read Data From Each Alarm] check box,
and specify [Number of Addresses] (for example, 3) to read the data
values.
-
Click the [Address1] cell, then click . The [Trigger
Condition Settings] dialog box appears.
-
Set the addresses to read the data values when Alarms
triggered.
-
Set the value in [Data Display Style], and click
[OK].
-
Specify [Bit Length] and [Data Type]. Alarm
settings have been completed.
-
Open the screen editor and set the Alarm part which
will display the Alarm. In the [Parts (P)] menu, select [Alarm
(A)], or click and place the Part on
the screen.
-
Double-click the placed Alarm. The Alarm dialog box
appears.
-
For the alarm, select the Block and the Display
Mode.
-
Set the [Display Start Row], [Display Alarms] and
[Display Row Spacing].
-
On the [Item] tab, select the [Address] check box
to set [Display Characters]. Select the [Address1], [Address2], and
[Address3] check boxes.
-
As needed, use the [Color] tab, and [Display] tab
options to change alarm message's number of display characters,
text color, background color, font, and size. Click [OK].