 I cannot download to a QPJ-2D100-x2P
   
The QPJ-xxxxx-xxx 5.7 inch models shipping after November 1, 2004 have been updated with a different memory chip. This change in memory chip requires two files within QuickDesigner software to be replaced with the following two files:
   
The two files are:
   
81001090.ild
81001090.spg
   
Please perform the following actions before downloading an application from your QuickDesigner software:
   
Step 1: Unzip the two files into a temporary directory.
   
Step 2: Locate the directory in which you have installed your QuickDesigner software and locate a subfolder named, "Panel".
   
The default software installation location is: C:\quick\Panel
   
Step 3: Remove and backup the existing two filenames that match the files listed above from the "Quick\Panel\" directory. Save these files in case you have a problem with this procedure.
   
Step 4: Copy the two files listed above from the temporary folder into the "Quick\Panel" Directory. These files are to replace the existing (renamed) files and will work with both older QPJ revision units plus the new units.
   
Step 5: Verify you have completed the above steps properly by downloading a very simple text screen or object to the QPJ unit. If the application downloads without encountering any problems you should be able to download your standard application as well.
   
Warning: QuickDesigner is not supported in Windows XP or Vista. Downloading a QuickDesigner project with an XP system may corrupt your HMI's firmware.
   
QPJ-2D100-L2P, QPJ-2D100-S2P