If the maximum number of Alarm History messages that can be stored is 768, why can I store only about 100?
There is a setting related to the stored number of Alarm Messages. Pease check the following settings:

1. Click [GP Setup]→[Extended Settings]→[Q Tag Settings]
 
   
2. Set the total number of [Active], [History], [Log] of [Q Tag Settings] to be 768. If you use only [History], you can set it up as shown below:
 
  If you use [Block] functions, set the total number of Alarm Messages used in all blocks to be 768.
 
3. Transfer the Project File to the GP unit again. When transferring, open [Transfer] →[Setup] →[Transfer Settings], and verify that [GP System Screen] is checked.
 
 
 
 
 
 
Return to Top Back