| If the maximum number of Alarm History messages that can be stored is 768, why can I store only about 100? |
 |
 |
|
| There is a setting related to the stored number of Alarm Messages. Pease check the following settings: |
| 1. |
Click [GP Setup]→[Extended Settings]→[Q Tag Settings] |
| |
 |
| |
|
| 2. |
Set the total number of [Active], [History], [Log] of [Q Tag Settings] to be 768. If you use only [History], you can set it up as shown below: |
| |
 |
| |
If you use [Block] functions, set the total number of Alarm Messages used in all blocks to be 768. |
| |
 |
| 3. |
Transfer the Project File to the GP unit again. When transferring, open [Transfer] →[Setup] →[Transfer Settings], and
verify that [GP System Screen] is checked. |
| |
|
|
| |
| |
|
| |
| |
| |
|