| Web Server cannot be used without first being set up. In the System Settings window, select
[Display Unit] -> [Remote Viewer] -> [Enable Web Server]. Please check this setting before transferring the project. |
|
Set up no more than 90 single-byte characters for the destination path of the standard
HTML template and FTP server. To use the Web Server standard HTML template, be sure to transfer the standard
HTML template to the display unit. The Standard HTML template is installed in the following location.
C:\Program Files\Pro-face\GP-Pro EX 2.1\HTMLContents
For transfer methods, click here. |
|
| You cannot transfer the standard HTML template when the AGP has not been initialized. In
any project, check [Enable Web Server] and transfer it to the AGP. Next, use the Transfer Tool [Send Web site]
command to transfer the standard HTML template. |
|
| The system program on the display unit (Runtime) must be GP-Pro EX Ver.2.10 or later or you
cannot transfer the standard HTML template to the display unit. |
|
| The number of computers that can access Web Server at the same time depends on the AGP model.
With the AGP3400, 3500, 3600, and 3700 Series, three computers can access at the same time. As for the AGP3200
and 3300 Series, as long as there are no memory issues, access is available only one computer at a time. |
|
| You cannot customize the content in the [Device Information] main frame. |
|
| The maximum number of alarms you can display on one [Alarm Information] page is 15. |
|
| The maximum number of alarms you can display on RSS is 15. |
|
| When Internet Explorer display settings are changed such as the text size, the standard HTML
may not display properly. |
|
| When using Web Server on the AGP3200 or 3300 Series, 1 MB from the User Screen Area is
allocated to Web Server. As a result, Web Server adds 1 MB to the send data size. |