>2011 > June 24 Important notice to customers who use GP-Pro EX Ver. 2.7Thank you very much for your continuous use of Pro-face products. We have confirmed that the following symptoms occur in GP-Pro EX Ver. 2.7.
The symptom and corrective means for this problem are indicated below. We sincerely apologize for any inconvenience this may cause you.
Symptom 1
Hang-up or system error might occur to GP when used in the following conditions.
When the user function is used in any of the script features in the user-created screen in the following operations: - Screen Change is executed frequently. - GP is used for long hours continuously. (e.g. 24-hour operation) Applicable product combination
Applicable when the following products are used in combination.
Screen Editor Software "GP-Pro EX" :
Measures
[Workaround]
When the aforementioned symptom occurs, turn off the GP and then restart it. [Permanent Measure] The fixed version (Ver. 2.70.100) was uploaded to our website in June 6, 2011. -> GP-Pro EX Ver. 2.70.100 Update Module Symptom 2Although you make a choice of a storage frequency for the alarm history, the setting of one minute is automatically set.
There is no problem found in other functions or performance.
Applicable product combination Applicable when the following products are used in combination.
Screen Editor Software "GP-Pro EX" :
Model :
MeasuresThe fixed version (Ver. 2.70.100) is posted on our website.
-> GP-Pro EX Ver. 2.70.100 Update Module * To download the module, free member registration for “Otasuke Pro!” is required. Click here to register. [Attention] Please set the storage frequency again in the editor, and transfer the screen data. InquiryIf you have any inquiries, please contact our sales office in your region. For contact information, please refer to "Our Locations" page.
|